0010456_A1
ABNOX Temperature Controller AXTR-xxxxxx-xxxxx
Page 75 of 84
Fixed limit value
AF7
AF8
Timer (tFCt)
The timer issues an outlet signal which is available for the binary functions. This will help you realize e.g. a
time-limited controlling or a time-dependent switching of the desired value. The timer value will not be saved
during a power outage. The time remains inactive after the return of current.
ConF
-
>
tFCt
-
>
Parameter
Value
Description
Function
FnCt
0
Timer turned off
1
Timer signal is “high“ while timer is running
2
Timer signal is “low“ while timer is running
Start condition
Strt
0
Manual start through function key or binary signal (no re-
start after power outage)
1
Automatic start after ‘power on‘ (restart after power out-
age); manual start also possible
Time unit
Unit
0
mm:ss
1
h:mm
2
hhh.h
Timer value
t1
00.00.
...
999.9.
Runtime of timer (in the preset time unit)
Tolerance band
toLt
0
... 9999
Tolerance band for the start of the timer. The timer will not
start before the actual value hasn’t reached the tolerance
band. 0 = start without tolerance band
1
0
X
AL
HySt
1
0
X
AL
HySt