25
BATTERY OPERATION
During power failure....
The operator and devices connected will operate normally. The red LED starts
to blink.
17 V
20 V
WHEN BATTERY VOLTAGE DROPS UNDER
The operator halts
Low-energy state:
The door is opened manually
and the operator closes door.
24 V Full battery backup
; The operator and devices connected will operate during
a power failure. The operation time depends on number of openings and the current
draw of the devices fitted.
15 V
26 V
BATTERY VOLTAGE
When battery backup use is chosen, the battery is checked by the operator and the
following should be noted:
Battery operation is
set to 12V battery
The battery is tested if the
voltage rises above 26 V it
is operational.
If the voltage does not rise
above 26 V in 24 hour period,
the battery should be
replaced
The operator tests
the battery
The test made by the operator:
The battery is loaded with 0.8 A test load for a
10 second period. If the battery voltage drops under 23 V, the battery is
found unsuitable => a red LED flashes at the end of the operator indicating this
state.
The red LED stops blinking.If the operator stays in low-energy state, one manual
opening is required to re-enegise the operator to chosen program selector mode.
When power failure ends....
Note !
In battery use the continious load in 24V output must not exceed 200 mA.
Do not use the Lock-up force (control point 11).