![background image](http://html1.mh-extra.com/html/ablerex/kronos/kronos_installation-and-operation-manual_3045784055.webp)
53
3.4.4
Switch to bypass
(1)
Select
→Command→Operation→Loadon Bypasson LCD display.
(2)
The Inverter will be shutdown and the bypass will supply the power to the load. If the
battery is disconnected, Rectifier and Charger will be shutdown as well.
3.4.5
Switch from normal mode to maintenance bypass
(1)
Select
→Command→Operation→Loadon Bypass on LCD display.
(2)
The Inverter will be shutdown and bypass will supply the power to the load.
(3)
Open/disconnected the external battery Switch/fuses if equipped.
(4)
Close the maintenance bypass switch.
(5)
Select
→Command→Operation→Shutdown on LCD display.
(6)
Open Output and Mains/Bypass Input breaker.
(7)
On the rear of UPS, switch OFF
AC Power
and
Batt. Power
switches.
3.4.6
Maintenance bypass → normal mode
(1)
On the rear of UPS, switch ON
AC Power
switch to start the working Power.
(2)
Close the Output and Mains /Bypass Input breaker.
(3)
Select
→Command→Operation→Loadon Bypass on LCD display.
(4)
Open maintenance bypass breaker.
(5)
Select
→Command→Operation→Normal Mode on LCD display.
(6)
Return to Mimic Display. Wait for a few minutes, the rectifier will start and the icon
will show you when can close the Battery line switch/fuses to connect the batteries.
Summary of Contents for KRONOS
Page 1: ...KRONOS 208V 10 40kVAUPS Installation and Operation Manual...
Page 11: ...9 10kVA Right Side View 850mm...
Page 12: ...10 15 20kVA Right Side View 850mm...
Page 13: ...11 30 40kVA Right Side View...
Page 17: ...15 10kVA Internal Right View 1 1 Battery Tray...
Page 18: ...16 15 20kVA Internal Right View 1 1 Battery Tray...
Page 24: ...22 15 20kVA 30 40kVA...
Page 26: ...24 15 20kVA 30 40kVA...
Page 27: ...25 Raise the wheel brakes to remove the UPS 10kVA 15 20kVA Wheel Brake Wheel Brake...
Page 28: ...26 30 40kVA Block the wheel brakes to secure the UPS 10kVA Wheel Brake Wheel Brake...
Page 29: ...27 15 20kVA 30 40kVA Wheel Brake Wheel Brake...
Page 30: ...28 Follow this step to secure the UPS 10kVA 15 20kVA...
Page 31: ...29 30 40kVA...
Page 39: ...37 UPS in parallel using a common battery Load 3P N...
Page 47: ...45 Parallel communication cables connected are shown below...
Page 52: ...50 3 4 Operating Processes 10kVA 15 20kVA 30 40kVA...
Page 71: ...69...
Page 72: ...70 192321272020003...