44
2.7
UPS Parallel Connections (Option)
The Kronos UPS may be operated in parallel to increase it's capacity and also adds redundantcy
and increases the systems reliability.
Up to 6 UPS units may be connected and operated in parallel.
Each UPS requires the additional of the parallel card (Option).
The size and length of the AC input and output cables must be identical for all UPS units.
The phase rotation must be the same for each UPS unit.
It is recommended to use an external bypass cabinet to facilitate maintenance and system
testing for parallel operation system.
Parallel configuration must be performed by authorized and qualified technicians who are
familiar with this the Kronos UPS.
Parallel cables must installed in order for each to UPS to communicate with each other.
Only use the parallel communication cables which are supplied with Kronos UPS to ensure
that the UPS will operate properly in a parallel configuration.
The parallel communication cables must be connected in a ring configuration. The
maximum total length of the parallel communication cables must be less than 38 meters. To
ensure good communication quality you must set the Switch & SW3 of the two furthest
UPS to the “ON” position as shown in below. (Please reference to section 2.6 for SW3)
Summary of Contents for KRONOS
Page 1: ...KRONOS 208V 10 40kVAUPS Installation and Operation Manual...
Page 11: ...9 10kVA Right Side View 850mm...
Page 12: ...10 15 20kVA Right Side View 850mm...
Page 13: ...11 30 40kVA Right Side View...
Page 17: ...15 10kVA Internal Right View 1 1 Battery Tray...
Page 18: ...16 15 20kVA Internal Right View 1 1 Battery Tray...
Page 24: ...22 15 20kVA 30 40kVA...
Page 26: ...24 15 20kVA 30 40kVA...
Page 27: ...25 Raise the wheel brakes to remove the UPS 10kVA 15 20kVA Wheel Brake Wheel Brake...
Page 28: ...26 30 40kVA Block the wheel brakes to secure the UPS 10kVA Wheel Brake Wheel Brake...
Page 29: ...27 15 20kVA 30 40kVA Wheel Brake Wheel Brake...
Page 30: ...28 Follow this step to secure the UPS 10kVA 15 20kVA...
Page 31: ...29 30 40kVA...
Page 39: ...37 UPS in parallel using a common battery Load 3P N...
Page 47: ...45 Parallel communication cables connected are shown below...
Page 52: ...50 3 4 Operating Processes 10kVA 15 20kVA 30 40kVA...
Page 71: ...69...
Page 72: ...70 192321272020003...