18
18
Alarm control
Alarm on (default)
Alarm off
19
Automatically return to
default display screen
Return to default
display screen
(default)
If selected, no matter how users
switch display screen, it will
automatically return to default display
screen (Input voltage /output voltage)
after no button is pressed for 1
minute.
Stay at latest screen
If selected, the display screen will stay
at the latest screen user finally
switches.
20
Backlight control
Backlight on (default)
Backlight off
22
Beeps while primary source
is interrupted
Alarm on (default)
Alarm off
23
Overload bypass:
When enabled, the unit will
transfer to line mode if
overload occurs in battery
mode.
Bypass disable
(default)
Bypass enable
25
Record Fault code
Record enable
Record disable (default)
26
Bulk charging voltage
(C.V voltage)
default setting: 28.2V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 24.0V to 29.2V. Increment of each
click is 0.1V.
27
Floating charging voltage
default setting: 27.0V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 24.0V to 29.2V. Increment of each
click is 0.1V.
29
Low DC cut-off voltage
default setting: 21.0V