separate DC over-current protector or disconnect the device between battery and inverter. It may not be
necessary to disconnect the device for
some applications, however, it’s
requested to have over-current
protection installed. Please refer to the typical amperage in the table below as required fuse or size of the
breaker.
WARNING!
All wiring must be performed by a qualified personnel.
WARNING!
It's very important for system safety and efficient operation to use appropriate cable for battery
connection. To reduce risk of injury, please use proper cables and suitable size of terminal recommended below.
Recommended battery cables and size of terminal:
Model
Typical Amperage
Battery Capacity
Wire Size
Torque Value
3KVA 24V
100A
100AH/200AH
1*4AWG
2~ 3 Nm
Please follow the steps below to implement the battery connection:
1.
Remove insulation sleeve 18 mm for positive and negative conductors.
2.
Suggest to put bootlace ferrules on the end of positive and negative wires
with a proper crimping tool.
3.
Fix strain relief plate to the inverter by supplied screws as shown in below
chart.
4.
Connect all battery packs as below chart.
5.
Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with
torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is
correctly connected and conductors are tightly screwed into the battery terminals.
Recommended tool: #2 Pozi Screwdriver