EN - 22
BAL.0713.0 • 2019-02-11
6 Commissioning
TCS-FP
6.6.8 TCS-FP microcontroller PCB
If safety devices (e.g., emergency stop switch)
are not used
, a jumper between terminal clamps A and B as well as
between C and D must be integrated; or sliding switches E and F must be switched to the ON position.
If safety devices (e.g., emergency stop switch)
are used
, sliding switches E and F must be switched to the OFF position.
The safety device must connect clamps A and B (24-V operating voltage) and clamps C and D (GND) in operating mode.
Fig. 15
TCS-FP microcontroller PCB
1
2
3
5
6
7
8
9
10
11
A
B
C
D
E
F
4
12
13 14 15 16
LED Color
Status Description
1
Green
On
“Start+” signal is active
Off
“Start+” signal is not active
2
Green
On
“Start+” signal is active
Off
“Start+” signal is not active
3
Orange
On
“Ready” output is active
Off
“Ready” output is not active
4
Green
On
“S3 collet is closed” end switch was tripped
Off
“S3 collet is closed” end switch was not tripped
5
Green
On
“S4 stroke cylinder is up” end switch was tripped
Off
“S4 stroke cylinder is up” end switch was not tripped
6
Green
On
“S1 stroke cylinder is down” end switch was tripped
Off
“S1 stroke cylinder is down” end switch was not tripped
7
Green
On
“S2 collet is open” end switch was tripped
Off
“S2 collet is open” end switch was not tripped
8
Orange
On
“Y2 close clamping cylinder and motor on” output is active
Off
“Y2 close clamping cylinder and motor on” output is not active
Tab. 14
LED status module
Summary of Contents for TCS-FP
Page 4: ...DE 4 BAL 0713 0 2019 02 11 1 Identifikation TCS FP ...
Page 5: ...TCS FP 1 Identifikation BAL 0713 0 2019 02 11 DE 5 ...
Page 34: ...EN 4 BAL 0713 0 2019 02 11 1 Identification TCS FP ...
Page 35: ...TCS FP 1 Identification BAL 0713 0 2019 02 11 EN 5 ...
Page 64: ...ES 4 BAL 0713 0 2019 02 11 1 Identificación TCS FP ...
Page 65: ...TCS FP 1 Identificación BAL 0713 0 2019 02 11 ES 5 ...