5. The control board could be defective

6. The upper casing is not tightly tied to the lower casing.

C. If there is no dehumidification at all with the air mover running just fine but the 

compressor is stalled, check

1. Defective connection in the compressor circuit
2. Defective compressor or an overload
3. A defective control motherboard
4. Defective capacitor in the compressor
5. Defective compressor
6. Closed safety float switch. In this case, check the 
status of the reservoir

D.  If the air mover fails to run with the compressor running intermittently, check

1. If there is a loose connection in the blower circuit
2. If there is an obstruction that prevents the impeller from rotating
3. The air mover may be defective

E. If there is some dehumidification but you notice it is way below what you expect, check

1. If the humidity sensor is defective
2. The measurement for temperature and or humidity is not calibrated properly
3. The humidity and or temperature have reduced
4. The defrost thermistor could be defective

F. If the dehumidifier is running but isn’t pumping water, check 

1. If the motor of the pump is defective
2. If the hose is not plugged in or is twisted
3. If there is a bad connection within the circuit of the pump
4. Check the float switch
5. If there is an internal disconnection of the hose
6. If the valve for pump check is plugged

G. When the dehumidifier automatically pumps water but does not do so when you push 
the PURGE button, check if

1. There is a bad connection within the circuit of the purge button
2. The control board is defective

H. Of the evaporator coil continuously frosts, with a low capacity of dehumidification, check

1. If the defrost thermistor is defective or loose
2. If the refrigerant charge is low

3. If the air filter  is dirty or the airflow is restricted
4. The front casing is not tied to the rear one

I. If the compressor runs with its air button turned off, check if

1. The control board is defective

AirMover

The impeller causes the air to move
If it is defective, the whole assembly should be replaced, 

1. Remove the power cable from the power socket
2. Pull out the exhaust and the control board
3. Remove the impeller bracket
4. Disconnect the leads of the impeller
5. Undo the impeller screws holding it to the mounting plate
6. Put the new impeller together by reassembling it step by step in the reverse of the 
above process

Thermistor Probe

1. Unplug the unit
2. Remove the housing at the top
3. Pull the probe of the thermistor up and remove it from the evaporator coil
4. Remove the cover of the evaporator control board
5. Unwind the thread wire of the thermistor from its harness
6. Remove the thermistor probe connector

The thermistor senses the temperature of the evaporator coil. It is inserted through 
the top of the evaporator coil. If you wish to replace the thermistor,

7. Assemble the probe of the thermistor and humidifier by reversing the steps outlined above.

Troubleshooting

A. Conduct checks and the following procedures below if you experience any of the following 

problems with your unit: if the unit does not dehumidify at all, if its controls do not light up, or if 

the unit does not turn on at all.

1.See if the cable of the unit is unplugged or if there is no power supply to the outlet you 
are using. If these are alright,

2.Check the control board or

3.Check if there is a loose connection in the wiring inside the unit

B. If the compressor runs erratically, even though there is some dehumidification and the 

air mover without stopping.

1. The dehumidifier is in the defrost cycle
2. The defrost sensor is defective or even loose
3. There is a loose connection inside, most likely in the circuit of the compressor
4. The compressor may be defective or even overloaded

12

13

Summary of Contents for SLGR Elite

Page 1: ...fier User sManual Note as we keep upgrading our product we reserve the right to modify the product without natice in advance Abestorm Solutions INC Water Damage Series Add Berlin Tel 44 20 81243974 Email www abestorm com ...

Page 2: ...at can instant detect the room and provide instant feedback With a superior stacking and a heavy duty condensate pump These stackable dehumidifiers are the best drying system Read the operation and maintenance instructions carefully before using this unit Proper adherence to these instructions is essential to obtain maximum beneft from your Abestorm SLGR Elite dehumidifer It is designed to be used...

Page 3: ...our local installer or Contact Abestorm sales Abestorm com or 44 20 81243974 Electrical Supply Power Supply Outlet Requirement Citcuit protector WARNING Using a 220V outlet may cause serious injury from electric shock To reduce risk of injury 1 Always disconnect machine from electrical power before servicing 2 Only plug unit into a gounded electrical cicuit 3 Do not use an extension cord 4 Do not ...

Page 4: ...k or even to a container that can collect the discharged water Control Panel When the unit is plugged in you will see the Abestorm LOGO STARTUP Press the POWER button to turn the dehumidifier ON and OFF Press the PURGE button to purge the machine Press the MENU button to advance to the next screen or to enter a value Press the SET button to scroll through available values The machine displays when ...

Page 5: ...7 6 ...

Page 6: ...rt causes clogging in the system Instructions for use of filter 9 8 E1 Humidity Sensor or Communication Error Solution Check to ensure that the sensor wire is connected at both ends if no issues are visible the sensor may be faulty E4 Problem with Pump Solution Verify that the pump is properly installed and functioning If so unplug the unit for two minutes then restart Solution Increase the room t...

Page 7: ...r back and pour a cup of 8oz of an antifreeze reagent with Propylene glycol Put it via the heat exchanger It will stream into the reservoir of the pump Avoid purging the solution from the unit 5 If filters are dirty they should be replaced if the unit is going to be stored for a long time This precaution will prevent microbial from growing on the filter Technical Description The unit a system of r...

Page 8: ...y or the airflow is restricted 4 The front casing is not tied to the rear one I If the compressor runs with its air button turned off check if 1 The control board is defective AirMover The impeller causes the air to move If it is defective the whole assembly should be replaced 1 Remove the power cable from the power socket 2 Pull out the exhaust and the control board 3 Remove the impeller bracket ...

Page 9: ...nit from the power source 2 Remove the housing at the top 3 Disconnect the float switch cables from their harness 4 Remove the screw that ties the bracket of the pump to the housing at the bottom 5 Remove the float switch from the bracket by unscrewing The pump is activated by the float safety switch when the water level in the condensate pump has risen too high The switch is also responsible for ...

Page 10: ...r and palletizing 2 Reinstallation and removal of the unit will be done by the owner 4 The customer is also responsible for risks related to damage and loss while shipping If shipped customer is responsible for all risk of loss or damage 2 If there is a need for warranty service the customer should contact Abestorm Tech Support on to get an RA Return Authorization number 44 20 81243974 3 After you...

Page 11: ...ALLATION OR DESIGN FAILURE TO FOLLOW INSTRUCTIONS LACK OF NORMAL CARE TAMPERING MISUSE OR ABUSE WHETHER ACCIDENTAL OR INTENTIONAL FIRE HURRICANE STORM DAMAGE 3 ANY COSTS DUE TO LOST PROFIT OR DELAY 5 ANY ADDITIONAL COSTS DUE TO CHANGES IN LAWS OR BUILDING CODES 4 FREEZING 6 FREIGHT CHARGES 7 CORROSION 8 CAUSE BEYOND CONTROL 9 FILTERS 10 CONSUMABLE PARTS INCLUDING BUT NOT LIMITED TO SWITCHES POWER ...

Reviews: