background image

12 

ABBRA INSTALLATION 

Table 1 - DEFAULT AND PROGRAMMED ZONE DEFINITIONS 

Zone 

Zone Type 

Zone Name 

Chime (melody 

No. 

Default

 

Programmed

 

Default 

Programmed  Zone Name or Off) (*) 

1   

Delay 1 

 

Front Door 

 

 

2   

Delay 1 

 

Garage 

 

 

3   

Delay 2 

 

Garage Door 

 

 

4   

Perimeter 

 

Back Door 

 

 

5   

Perimeter 

 

Child Room 

 

 

6   

Interior 

 

Office 

 

 

7   

Interior 

 

Dining Room 

 

 

8   

Perimeter 

 

Dining Room 

 

 

9   

Perimeter 

 

Kitchen 

 

 

10  

Perimeter 

 

Living Room 

 

 

11  

Interior 

 

Living Room 

 

 

12  

Interior 

 

Bedroom  

 

 

13  

Perimeter 

 

Bedroom  

 

 

14  

Perimeter 

 

Guest Room 

 

 

15  

Interior 

 

Master Bedroom 

 

 

16  

Perimeter 

 

Master Bedroom 

 

 

17  

Perimeter 

 

Laundry Room 

 

 

18  

Perimeter 

 

Master Bathroom   

 

19  

Perimeter 

 

Basement 

 

 

20  

Fire 

 

Fire 

 

 

21  

Fire 

 

Fire 

 

 

22  

Emergency 

 

Emergency 

 

 

23  

Emergency 

 

Emergency 

 

 

24  

24 h / silent 

 

Basement 

 

 

25  

24 h / silent 

 

Office 

 

 

26  

24 h / audible   

Attic 

 

 

27  

24 h / audible   

Den 

 

 

28  

non-alarm 

 

Yard 

 

 

29  

non-alarm 

 

Hall 

 

 

30  

non-alarm 

 

Utility room 

 

 

* Note:

 All zones are Off-chime by default. Enter your own choice in the last column and program accordingly

 

 

4.4 DEFINING CONTROL PANEL PARAMETERS 

4.4.1 Preliminary Guidance  

This  mode  allows  you  to  customize  the  control  panel  and 
adapt  its  characteristics  and  behavior  to  the  requirements 
of  the  particular  user.  An  illustrated  process  is  shown  in 
figure  4.4.  In  this  illustration,  each  selected  option  is 
displayed  with  a  dark  box  at  the  right  side.  To  review  the 
options,  repeatedly  press  <

Next

>  or  <

Back

>  button,  until 

the  desired option is displayed, then press <

View/Select

button

.

 

4.4.2 Entry Delays 1&2 

(fig. 4.4, location 01, 02)

 

Two  different  entry  delays  allow  the  user  to  enter  the 
protected site (while the system is in the armed state) via 2 
specific doors and routes without causing an alarm.  
Following  entry,  the  user  must  disarm  the  control  panel 
before  the  entry  delay  expires.  Slow-rate  warning  beeps 
start  sounding  once  the  door  is  opened,  until  the  last  10 
seconds  of  the  delay,  during  which  the  beeping  rate 
increases.  Locations  No.  1  (entry  delay  1)  and  2  (entry 
delay  2)  allow  you  to  program  the  length  of  these  delays. 
Available  options  for  each  delay  are: 

00s

15s

30s

45s

60s

 , 

3m 

and

 4m

In UL installations, these delays must be 45 s max.

  

4.4.3 Exit Delay 

(fig. 4.4 location 03)

 

 

An exit delay allows the user to arm the system and leave the 
protected site via specific routes and doors without causing an 
alarm.  Slow-rate  warning  beeps  start  sounding  once  the 
arming command has been given, until the last 10 seconds of 
the  delay,  during  which  the  beeping  rate  increases.  Location 
No.  3  allows  programming  of  the  exit  delay  length. Available 
options are: 

30s

60s

90s

120s

3m,

 

4m

In

 

UL

 

installations, set exit delay to 30 or 60 seconds. 

4.4.4 Bell Time 

(fig. 4.4, location 04)

 

Here  you  select  the  length  of  time  the  bell  (or  siren)  is 
allowed  to  function  upon  alarm.  The  bell  time  starts  upon 
activation of the siren. Once the bell time expires, the siren 
is automatically shut down. 
Available options: 

1

3

4

8

10

15

 and 

20

 minutes.  

In

 

UL

 

installations, set bell time to 4 minutes minimum, 

in canadian installations, set bell time to 8 minutes. 

4.4.5 Abort Time 

(fig. 4.4 location 05)

 

Do not use in UL

 

installations. 

Here you select the length of time allowed by the system to 
abort  an  alarm  (not  applicable  to  alarms  from  FIRE,  24H 
SILENT,  EMERGENCY,  GAS  and  FLOOD  zones).  The 
Abbra  is  programmed  to  provide  an  “abort  interval”  that 
starts  upon  detection  of  an  event.  During  this  interval,  the 
buzzer sounds a warning but the siren remains inactive and 
the  alarm  is  not  reported.  If  the  user  disarms  the  system 
within the allowed abort interval, the alarm is aborted. 
Available options: 

00s

15s

30s

45s

60s

2m,

 

3m

4m

4.4.6 Alarm Cancel 

(fig. 4.4, location 06)

 

Here  you  determine  the  ”cancel  alarm”  period  that  starts 
upon  reporting  an  alarm  to  the  central  station.  If  the  user 
disarms  the  system  within  that  time  period,  a  “cancel 
alarm” message is sent to the central station. 
The  options  are: 

1

5

15

60

 

minutes

4

 

hours

  and  also 

cancel inactive

Summary of Contents for Fully Supervised Wireless Alarm Control System

Page 1: ...eliminary Guidance 11 4 4 2 Entry Delays 1 2 11 4 4 3 Exit Delay 11 4 4 4 Bell Time 11 4 4 5 Abort Time 11 4 4 6 Alarm Cancel 11 4 4 7 Quick Arm 12 4 4 8 Bypass 12 4 4 9 Exit Mode 12 4 4 10 Piezo Beeps 12 4 4 11 Trouble Beeps 12 4 4 12 Panic Alarm 12 4 4 13 Swinger Stop 12 4 4 14 Cross Zoning 12 4 4 15 Supervision 12 4 4 16 NOT READY 12 4 4 17 AUX Button 12 4 4 18 Jam Detect 12 4 4 19 Latchkey 12 ...

Page 2: ...to the master user after testing the system Appendices A 1 and A 2 will help you prepare an installation plan Please take time to fill out the forms your job will become much easier and confusion will be prevented Filling out the forms will also help you create a list of detectors and transmitters that must be obtained for the particular application Compatible detectors and transmitters are listed...

Page 3: ...arm in accordance with zone attributes Siren Signals Continuous intrusion 24 hours panic triple pulse pause triple pulse fire Siren bell Timeout Programmable 4 min by default Internal Sounder Output At least 85 dBA at 10 ft 3 m Supervision Programmable time frame for inactivity alert Special Functions Speech and sound control Powerline Carrier Device Control up to fifteen X 10 brand units by vario...

Page 4: ... to Pager PIN No èAlarm Type èZone No 2 5 Physical Properties Operating Temp Range 32 F to 120 F 0 C to 49 C Storage Temp Range 4 F to 140 F 20 C to 60 C Humidity 85 relative humidity 30 C 86 F Size 10 13 16 x 8 x 2 1 8 in 275 x 203 x 55 mm Weight 990g 2 2 pounds without batteries Color Ivory and charcoal gray 3 INSTALLATION 3 1 Unpacking the Equipment Open the cardboard packing box and check whet...

Page 5: ...INSTALLATION GUIDE Version 04 4 12 17 5 Figure 3 1 Backup Battery Installation Open cover 1 Keypad cover 2 Remove screw and open battery compatment Remove screw to release wall mount bracket Connect battery 3 ...

Page 6: ...6 ABBRA INSTALLATION Figure 3 2 Mounting the Control Panel ...

Page 7: ...eries has simple phone X 10 and AC power jacks pre installed No power or phone wiring is required simply plug the AC power cord into the AC power jack the phone cord into the telephone jack and the X 10 cord into the X 10 jack as applicable This schematic is provided for reference and for use in hard wiring sensors to zones 29 and 30 ...

Page 8: ...o 1 3 8 Connecting Abbra to Computer The control panel can be equipped with an optional RS232 module for serial data interchange with a local computer If this module is not supplied a special plastic cap blocks the niche designed to accommodate the module RJ 45 or RJ 31X USA 1 Remove plastic cap Insert the RS 232 adapter into its male connector until a click is heard 2 Figure 3 4 Connecting the Ab...

Page 9: ...ireless siren Before beginning gather all the devices that you intend to enroll and make sure they all have batteries installed Your control panel must recognize the unique identification code ID of each such device in order to supervise them receive their signals and respond accordingly Attention CodeSecure transmitters are mainly used for arming disarming and can not be enrolled to zones For enr...

Page 10: ...nrolling action NEXT OK ENROL WL SIREN NEXT WL siren No 1 or 2 e g 2 SIREN No siren No 2 siren No 2 OK OK OFF TO DELETE Momentarily press the wireless siren self test button until a squawk is heard 1 sec approx TRANSMIT NOW Enrolling a wireless siren siren No 2 for next enrolling action NEXT Deleting a wireless siren siren No 2 A W A Y 2way kp No 2 Deleting a wireless keypad MKP 150 Press MKP 150 ...

Page 11: ...olumns even before you start and proceed to program according to your own list Remember A delay zone is also a perimeter zone by definition Zone types are fully explained in Appendix D For UL installations hard wired zones are not intended to be used as FIRE zones Selectable Zone Names Dining room Downstairs Emergency Fire Front door Garage Garage door Guest room Hall Kitchen Laundry room Lving ro...

Page 12: ...ring which the beeping rate increases Locations No 1 entry delay 1 and 2 entry delay 2 allow you to program the length of these delays Available options for each delay are 00s 15s 30s 45s 60s 3m and 4m In UL installations these delays must be 45 s max 4 4 3 Exit Delay fig 4 4 location 03 An exit delay allows the user to arm the system and leave the protected site via specific routes and doors with...

Page 13: ...urs after having been bypassed if the system remains armed The available options are shut after 1 shut after 2 shut after 3 and no shutdown In UL installations No Shutdown must be selected 4 4 14 Cross Zoning fig 4 4 location 14 Do not use in UL installations Here you determine whether cross zoning will be active or inactive Cross zoning is a method used to counteract false alarms an alarm will no...

Page 14: ...ated The available options are enable and disable 4 4 28 Disarm Option fig 4 4 location 28 Here you determine when it is possible to disarm the system A Any time B During entry delay by using the Abbra keypad or wireless device keyfob C During entry delay byusing a wirelessdevice keyfob only D During entry delay or by using the PowerMax keypad in AWAY mode Options any time on entry all on entry wi...

Page 15: ... entry dly1 30 s entry dly1 45 s entry dly1 60 s entry dly1 3 m entry dly1 4 m abort time 00 s abort time 15 s abort time 30 s abort time 45 s abort time 60 s abort time 2 m abort time 3 m restart exit off by door normal NEXT OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK bell time 3 m NEXT NEXT abort time 4 m NEXT OK NEXT Note The currently saved options are displayed with dark box at t...

Page 16: ...waits 5 seconds F 5 Not applicable in phone numbers To enter a series of digits use the following keys Numeric keypad to enter the number Next Item moves the cursor from left to right Back moves the cursor from right to left Off deletes everything after the cursor to the right 4 5 1 Autotest Time fig 4 5 location 01 Here you determine the time at which the telephone line will be tested and reporte...

Page 17: ...the pager s address The paging company s computer needs this input for routing messages to the specific pager The PIN sequence precedes any digital message that the Abbra sends to the pager to report an event It may include digits pauses and special characters or Call the paging company to find out what the pager s PIN code should consist of Important In this location special characters can be ent...

Page 18: ...stalled or not installed Available options are installed or not installed 4 6 2 1st 2nd 3rd 4th SMS Number Here you define the first second third and fourth SMS phone number including area code 16 digits maximum to which pre selected events types see next paragraph will be reported 4 6 3 Reporting to SMS Phone Number Here you determine the types of events that will be reported to the pre selected ...

Page 19: ... 3 Defining INT STRB Here you determine if the INT output will be used for an internal siren or for a strobe 4 7 4 X 10 GENERAL DEF Not evaluated by UL For X 10 devices you can select the following actions n FLASH ON ALARM you can select no flash or all light flash to control X 10 lighting devices in alarm conditions n TRBL INDICATION you can select don t indicate or indicate for X 10 failure indi...

Page 20: ...T PGM NEXT PGM NEXT Dxx BY ARM AWAY Dxx BY ARM HOME Dxx BY MEMORY OK ONE WAY UNIT PLEASE WAIT test fail test OK NEXT TWO WAY UNIT OK OK OK OK to Enroll enroll OK Enroll FAIL enroll fail HOME Exit X 10 Learn mode OK OK Exit Learn Mode PLEASE WAIT OK to test OFF to Delete if already enrolled Turn X 10 to Learn mode NEXT OK OK pulse time 2s pulse time 30s pulse time 4m pulse time 2m Dxx PULSE TIME PG...

Page 21: ...ee fig 4 3 The recording process is shown below NEXT OK HOUSE IDENTITY 8 RECORD SPEECH see figure 4 1a USER 5 NAME NEXT USER 6 NAME NEXT USER 7 NAME NEXT USER 8 NAME RECORDING ENDED TALK NOW RECORD A MESSAGE e g John s house NEXT RECORD MESSAGE is displayed momentarily The dark square boxes slowly disappear one by one until end of recording time To check the recorded message press the key and list...

Page 22: ...em does not recognize your installer code this indicates you must have programmed a user code that is identical with your installer code If so access the user menu and change the code that is identical with your installer code This will re validate your installer code 4 11 RETRIEVING FACTORY DEFAULTS If you want to reset the Abbra parameters to the factory default parameters you should enter the i...

Page 23: ...roper function of all detectors in the system a comprehensive diagnostic test is required To perform this test refer to figure 4 9 5 3 Keyfob Transmitter Test Initiate transmission from each transmitter enrolled as a keyfob unit according to the list in Table A2 Appendix A Use each transmitter to arm the control panel AWAY and immediately disarm it Upon pressing the keyfob unit s AWAY key the ARM ...

Page 24: ...ttery pack correct insertion and tightened battery compartment lid the TROUBLE indicator should extinguish However the MEMORY message will now blink in the display caused by the tamper alarm you triggered when opening the battery compartment lid Clear it by arming the system and immediately disarming 6 3 Fuse Replacement The Abbra has two internal fuses that have automatic reset Therefore there is...

Page 25: ...Ψ 11 Gas Ψ 12 Flood Ψ 13 Interior Zone Locations Note down the intended location for each detector When programming you may select one of 26 available zone names plus 5 custom zone names that you can add see Figure 4 3 Define Zones Zones 29 30 only are hardwired zones A2 Keyfob Transmitter List Transmitter Data AUX button Assignments No Type Holder Status or Arming instant PGM Control X 10 Unit Co...

Page 26: ...List Tx Transmitter Type Enrolled to Zone Name of holder Assignment 1 2 3 4 5 6 7 8 9 10 APPENDIX B X 10 Unit and PGM Output Assignments Unit Controlled ON ON ON ON ON ON ON by Timer ON by Zone No ON No Appliance by arm HOME by arm AWAY by disarm by Memory by Delay by Keyfob ON Time OFF Time a b c by line fail 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 PGM ...

Page 27: ...ood alarm restore FT Fire Detector Clean XR Sensor Battery Restore FJ Fire detector trouble XT Sensor Battery Trouble FR Fire Restore YR System Battery Restore GA Gas alarm YT System Battery Trouble Disconnection GR Gas alarm restore YX Service Required GT Gas trouble 4 2 Event Codes Note Wireless siren reports to central station on zone 31 or 32 GSM reports to central station on zone 33 Alarms Zo...

Page 28: ...you choose to mute them Exit Delay The exit delay begins once the user arms the system It allows him to leave via interior zones and a doorway before arming actually takes effect When the exit delay starts the buzzer beeps slowly and maintains a slow beeping rate until the last 10 seconds during which it beeps rapidly The Abbra has two types of delay zones for which different delay times may be se...

Page 29: ...s and anti tamper protection They therefore trigger an alarm in both armed and disarmed states 24 Hour Zone Silent Upon detection this zone initiates a silent alarm meaning that the sirens do not function Instead the Abbra dials telephone numbers and reports the event to central stations and or to private telephones as programmed 24 Hour Zone Audible Upon detection this zone initiates a siren alar...

Page 30: ...Y and HOME together for 2 sec initiates PANIC alarm Pressing AWAY for 2 sec initiates Latchkey arming DISARM AWAY AUX HOME MCT 234 B MCT 231 201 N A in North America Single button pendant units The MCT 231 Code Secure and the MCT 201 PowerCode can be enrolled to perform functions as shown Both units look alike MCT 231 201 Not UL listed C MCT 134 104 N A in North America 4 button hand held units MC...

Page 31: ...se to an incoming call In most but not all areas the sum of the RENs should not exceed five 5 0 To be certain of the number of devices that may be connected to the line as determined by the total RENs contact the telephone company to determine the maximum REN for the calling area If this equipment causes harm to the telephone network the telephone company will notify you in advance that temporary ...

Reviews: