Manual ZX0 HB 600 en - Revision 05 |
63
Fig. 4.5.2: Controls and displays of the voltage transformer device
1
Operating lever
2
Lock knob
3
Padlock (optional)
4
Direction of rotation indicator
5
Switch position indicator
6
Warning signs
7
Lock position for “ON” position
8
Lock position for “OFF” position
Achtung!
Spannungswandler-Abtrennvorrichtung nur in
spannungsfreiem Zustand betätigen.
- Schloss entfernen
- Rastknopf ziehen
- Betätigungshebel drehen bis
Rastknopf wieder einrastet
Attention!
Operating of the vt-isolating system
only under no-voltage condition.
- remove the padlock
- pull the lock knob
- rotate the operation lever up to the
stop till the lock knob arrests again.
1
2
3
4
5
6
6
7
8
The controls and displays of the voltage transformer isolating
device can be seen in figure 4.5.2. Observe the warning signs
(6). Check the switch position indicator (5). The isolating device
can be secured with a padlock (3). Remove the padlock prior to
operation.
Isolating the voltage transformers
To isolate the voltage transformers, pull out the lock knob (2) and
turn the operating lever (1) counter-clockwise as shown on the
direction of rotation indicator (4). Release the lock knob. Turn the
operating lever counter-clockwise until the lock knob engages in
the limit position of the isolating device.
?
When the lock knob engages in the limit position,
the dielectric strength of the isolating device
is ensured.
Secure the isolating device with a padlock in the “OFF” position
(8).
Connecting the voltage transformers
To connect the voltage transformers, pull out the lock knob (2) and
turn the operating lever (1) clockwise as shown on the direction of
rotation indicator (4). Release the lock knob. Turn the operating lever
clockwise until the lock knob engages in the limit position of the isolat-
ing device.
?
When the lock knob engages in the limit position, the
current carrying capacity of the isolating
device is ensured.
Secure the isolating device with a padlock in the “ON” position (7).