10. Technical data
10.1 Technical data, general
10.1.1 Technical data Control electronics
a) Binary inputs
The following applies to all 5 input channels:
•
Electrical isolation between all inputs and from
the electronics:
2,0 kV AC
•
AC/DC operation (any polarity for DC)
•
Response range at inputs -MO1, -MC and -MO2,
optionally
1
):
•
24 V –15% ...60 V +15% AC
24 V –30% ...60 V +15% DC
•
100 V –15% ...125 V +15% AC
100 V –30% ...125 V +15% DC
•
220 V –15% ...240 V +15% AC
220 V –30% ...240 V +15% DC
•
Response range -MU
2
) adjustable, see page 26
•
Response range -RL1:
•
24 V –15% ...240 V +15% AC
•
24 V –30% ...240 V +15% DC
•
Base load at input:
- 300
k
Ω
[-MU
2
), -RL1, -MO2]
3
)
- 14
k
Ω
(-MO1,
-MC)
•
Inputs protected from voltage surges.
b) Binary outputs
The following applies to all 5 input channels:
•
Electrical isolation between all outputs and
from theelectronics:
2,0 kV AC
•
Switching voltage:
max. 400 V AC or 300 V DC
•
Switching current: max. 6 A / 250 V AC
(resistive)
•
ON
resistance:
100
m
Ω
•
Switch outputs: NOC, NCC and fleeting contact
•
Duration of fleeting contact pulse: 100 ms
•
Output connections: varistors.
10.1.2 Technical data AC/DC converter
Input voltage ranges, optional:
•
Power pack A:
- 24 V –15% ...48 V +15% AC
- 24 V –15% ...60 V +15% DC
•
Power pack B:
- 100 V –15%...240 V +10% AC
- 110 V –15%...240 V +10% DC
Protection of power feed (must be ordered):
•
Power pack A:
- ABB Stotz m.c.b.: S 282 UC-K, 1.6 A
•
Power pack B:
- ABB Stotz m.c.b.: S 282 UC-K, 1.0 A
•
Power consumption on the input side during a
charging process: ca. 100 W
•
Power consumption in normal position: P < 10 W
•
Charging times of the capacitor (example for
DC voltage):
a) Initial charging on commissioning:
- Breakers to 25 kA:
max. 10s
- Breakers from 31.5 kA: max. 15s.
depending on the supply voltage.
In this time, the capacitor(s) is/are charged
to 80 V, and an ON-OFF operating cycle is
already possible at 72 V.
(The ”READY” lamp indicates readiness for
switching. A flashing “READY” lamp signals
recharging of the capacitor. Switching
readiness is enabled during that time).
b) Recharging after a switching operation to a
charge of 80 V: max. 5s.
1
) Different response ranges for individual inputs on request.
2
) Full version on the control module
3
) In general, with AC signals which are connected via long lines,
it
should
be
checked
whether
the
installed
base
load
of
300
k
Ω
is sufficient (mutual capacitive coupling!)