M ED I U M VO LTAG E P R O D U C T S
25
25
6.6. Types of withdrawable circuit
breakers available for
PowerCube modules
Complete the circuit breaker selected with the
optional accessories indicated on the following
pages.
Withdrawable circuit breaker - VM1/A/P-VM1/A/PW for PowerCube modules
6.7. Mechanism and electrical
operation
To operate the circuit breaker electrically, control
power must be available. The section entitled
Racking describes the application of control power
through the secondary disconnect when the circuit
breaker is in the Test and Connect positions.
1. Inspect the initial state of the circuit breaker to
determine the operations available.
a. Close/Open Indicator.
b. Circuit breaker position Test or Connect (or
control power applied externally if
withdrawn).
2. Energize Control Power.
a. Wait until “READY” lamp is on; approximately
two minute maximum depending on control
voltage with 48 V DC taking the longest
amount of time.
b. Circuit breaker is ready to perform C-O
operation.
3. Close the circuit breaker using the close push-
button or by electrical signal to the magnetic
actuator.
a. The magnetic armature moves down.
• Close/Open indicator changes to Closed.
• READY” lamp illuminates again after about
one second.
b. Circuit breaker is ready to perform O-C-O
operation.
4. Open the circuit breaker using the manual OPEN
push-button or by electrical signal to the
magnetic actuator.
a. The armature moves up.
• Close/Open indicator changes to Open.
• “READY” lamp will remain illuminated.
b. Circuit breaker is ready to perform C-O
operation.
Ur
Isc
Rated uninterrupted current (40°C) [A]
kV
kA
W = 600
W = 750
W = 750
Type of circuit breaker
P = 150
P = 210
P = 210
u/l = 205
u/l = 310
u/l = 310
ø = 35
ø = 35
ø = 79
PowerCube
PB1
PB2
PB2
15
25
1250
VM1/P 12.12.25 p150
31.5
1250
VM1/P 12.12.32 p150
25
1250
VM1/W 12.12.25 p210
31.5
1250
VM1/W 12.12.32 p210
25
2000
VM1/P 12.20.25 p210
31.5
2000
VM1/P 12.20.32 p210
W = Width of the switchgear.
P = Pole horizontal centre distance.
u/l = Distance between bottom and top terminal.
ø = Diameter of the isolating contact.