The geared motor automatically recharges the spring after each closing
operation until the yellow indicator (7) appears.
If the power is cut off during charging, the geared motor stops and
automatically starts recharging the springs again when the power
returns.
In any case, it is always possible to complete the charging operation
manually.
c) Circuit-breaker closing
The operation can only be carried out with the closing spring completely
charged.
For manual closing, press the pushbutton (5 - fig. 6b).
When there is a shunt closing release, the operation can also be
carried out remotely by means of a special control circuit. Closing
having taken place is indicated by the signalling device (6 - fig. 6b).
d) Circuit-breaker opening
For manual opening, press the pushbutton (4 - fig. 6b).
When there is a shunt opening release, the operation can also be
carried out remotely by means of a special control circuit. Opening
having taken place is indicated by the signalling device (6 - fig. 6b).