34
U N I S EC DI G ITA L
O P ER AT I O N A N D M A I N T EN A N C E M A N UA L
—
Annex 2
Sensor mounting for SFC unit on
cable connection
NOTE
Before performing any operation, please refer to
the UniSec 1VFM200005 panel operation and
maintenance manual
Temporary fixing of sensors on transport
insulators
• Sensors are temporarily fixed on insulators
mounted in hollow cell for transportation
• Mounting of the sensors on the main circuit must
be completed when the MV cables are connected
to the main circuit
• IMPORTANT: The sensors are already synchronized
with the concentrator, do not change the position
of the sensor with respect to the phase with which
it has been associated (see the positioning on the
back of the LV cell)
•
1. Connect the MV cables as shown in the UniSec
1VFM200004 installation manual.
2. Remove the sensor from the transport position.
Item
Description
1
Sensor
2
Probe cable
3
Plastic band