52
Installation and commissioning guide UCL/VUCL
|
1ZSC000562-AAZ en
9.6.2 Disk brake
For BUE:
Run the motor-drive mechanism and check again
that the red mark on the brake disk stops within the tolerance
of ± 25° from the exact position; see Fig. 24.
For BUL:
Run the motor-drive mechanism and check that the
center of the notch in the cam disk stops within ±2 mm from
the center of the roller on the brake arm; see Fig. 25.
For adjustment of the motor-drive mechanisms, see
the
maintenance guide: 1ZSE 5492-125 for UCL or
1ZSC000498-ABJ for VUCL
.
9.6.3 Counter
Check that the counter is functioning for RAISE and LOWER
operations.
9.6.4 Position transmitter and other position switches
Check the function of the position transmitter and other
position switches.
9.6.5 Light
Check that the light is switched on when the door is opened
and goes out when the door is closed.
9.6.6 Heater
Switch off all power sources and check with a finger that the
heater has warmed up during earlier tests. Switch on the
power afterwards.
9.7 Putting into operation
Set the LOCAL/REMOTE switch to REMOTE. Reset the drag
hands. Make sure that no tools or foreign objects are left in
the motor-drive cabinet or on the transformer cover. Close the
door to the motor-drive.