1ZSC000562-AAZ en
|
Installation and commissioning guide UCL/VUCL
13
1.6 Oil filter unit for continuous oil filtration
If the tap-changer should have an oil filter unit for continuous
oil filtration from ABB, installation and commissioning
instructions are found in the manual delivered with the unit.
1.7 Weights
– Motor-drive mechanism type BUE: approximately 155 kg
– Motor-drive mechanism type BUL2: approximately 95 kg
The weights of the motor-drive mechanism and drive-shaft
system are not included in the weights given in Tables 2
and 3.
On-load tap-changer
type designation
Approximate weight in kg
Tap-changer
without oil
1)
Required
oil
Total
UCL.N
380/600, 900
480
260
740
650/600, 900
500
300
800
1050/600, 900
510
340
850
UCL.T
380/600, 900
1230
3x260
2010
380/1800
1350
3x260
2130
380/2400
1440
3x260
2220
650/600, 900
1290
3x300
2190
650/1800
1410
3x300
2310
650/2400
1500
3x300
2400
1050/600, 900
1320
3x340
2340
1050/1800
1440
3x340
2460
1050/2400
1530
3x340
2550
UCL.B
380/600, 900
850
2x260
1370
650/600, 900
890
2x300
1490
1050/600, 900
910
2x340
1590
UCL.E
380/600, 900
410
260
670
380/1800
450
260
710
380/2400
480
260
740
650/600, 900
430
300
730
650/1800
470
300
770
650/2400
500
300
800
1050/600, 900
440
340
780
1050/1800
480
340
820
1050/2400
510
340
850
Table 2. Weights for type UCL.
1)
The weight of the diverter switch, approximately 120 kg, is included.
On-load tap-changer
type designation
Approximate weight in kg
Tap-changer
without oil
1)
Required
oil
Total
VUCL.N
380/600, 1000
510
260
770
650/600, 1000
530
300
830
1050/600, 1000
540
340
880
VUCG.T
380/600, 1000
1320
3x260
2100
650/600, 1000
1380
3x300
2280
1050/600, 1000
1410
3x340
2430
VUCL.B
380/600, 1000
910
2x260
1430
650/600, 1000
950
2x300
1550
1050/600, 1000
970
2x340
1650
VUCL.E
380/600, 1000
440
260
700
650/600, 1000
460
300
760
1050/600, 1000
470
340
810
Table 3. Weights for type VUCL.
1)
The weight of the diverter switch, approximately 150 kg, is included.
1.8 Tightening torques
The following tightening torques are recommended:
For metallic screw joints:
M6 .......... 10 Nm ±10 %
M8 .......... 24.5 Nm ±10 %
M10 ......... 49 Nm ±10 %
M12 ......... 84 Nm ±10 %
For non-metallic screw joints: M10 ......... 9 Nm
±10 %
M12 ......... 13 Nm ±10 %
M16 ......... 22 Nm ±10 %
if not otherwise stated in this guide.