TZIDC-110, TZIDC-120
DIGITAL POSITIONER | OI/TZIDC-110/TZIDC-120-EN REV. H
59
Para-
meter
Display
Function
Possible parameter setting
Unit
Factory setting
P7.5
GOPULS DOWN
Go pulse, down
0 to 200
msec 0
P7.6
Y-OFS UP
Y offset, up
Y offset (up)
Y-Min to 100.0
%
40.0
P7.7
Y-OFS DN
Y offset, down
Y offset (down)
Y-Min to 100.0
%
40.0
P7.8
---
---
P7.9
TOL_BAND
Tolerance band (zone)
Tolerance band (zone)
0.3 to 10.0
%
0.8
P7.10
TEST
Test
Test
Function
---
INACTIVE
P7.11
EXIT
Return
Return to operating level
Function
---
NV_SAVE
P8._, P9._,
P10._
P11._
FS / IP
P11.0
FAIL_POS
Save position
Safe position
ACTIVE, INACTIVE
---
INACTIVE
P11.1
FACT_SET
Factory setting
Factory setting
Function
---
---
P11.2
IP-TYP
I/P module type
Type of l/P module
NO_F_POS,F_SAFE_1,F_SAFE_2,
F_FREEZE1, F_FREEZE2
---
NO_F_POS
P11.3
EXIT
Return
Return to operating level
Function
---
---
* Activation by ABB Service only
Note
For detailed information on the parameterization of the device, consult the associated configuration and parameterization
instructions.