background image

  

TTH300

 | OI/TTH300-EN Rev. D  11

 

 

 

3.2

 

Installation instructions 

3.2.1

 

FM / CSA 

The installation, commissioning, maintenance and repair of 
devices in areas with explosion hazard must only be carried 
out by appropriately trained personnel. 
The operator must strictly observe the applicable national 
regulations with regard to installation, function tests, repairs, 
and maintenance of electrical devices. (e.g. NEC, CEC). 
 

3.2.2

 

IP protection rating of housing 

The temperature transmitter and LCD indicator types A and 
AS must be installed such that the IP rating of at least IP20 is 
achieved in accordance with IEC 60529. 
 

3.2.3

 

Electrical connections 

Earthing 

If, for functional reasons, the intrinsically safe circuit needs to 
be earthed by means of a connection to the potential 
equalization, it may only be earthed at one point. 
 

Intrinsic safety installation check 

If transmitters are operated in an intrinsically safe circuit, proof 
that the interconnection is intrinsically safe must be provided 
in accordance with IEC/EN 60079-14 as well as 
IEC/EN 60079-25.  
The supply isolators / DCS inputs must feature intrinsically 
safe input protection circuits in order to eliminate hazards 
(spark formation). 
In order to provide proof of intrinsic safety, the electrical limit 
value must be used as the basis for the EC-type examination 
certificates for the equipment (devices); this includes the 
capacitance and inductance values of the cables. 
Proof of intrinsic safety is said to have been provided if the 
following conditions are fulfilled when a comparison is carried 
out in relation to the limit values of the equipment: 
 

Transmitters 

(intrinsically safe equipment)

 

Supply isolator / DCS input 

(related equipment) 

U

i

 ≥ U

o

 

I

i

 ≥ I

o

 

P

i

 ≥ P

o

 

L

i

 + L

c

 (cable) 

≤ 

L

o

 

C

i

 + C

c

 (cable) 

≤ 

C

o

 

 

 

Field (Ex area) 

Control room (safe area) 

 

Fig. 6 

A

 Transmitter 

B

 Supply isolator / DCS input with supply / Segment 

coupler 

 

Installation in a potentially explosive atmosphere 

Transmitters can be installed in all kinds of industrial sectors. 
Potentially explosive systems are divided into zones, meaning 
that a wide range of different instruments are also required. 
For this, pay attention to the country-specific guidelines and 
certificates! 

 

NOTICE

 

Ex relevant specifications must be taken from the EC-type 
examination certificates and other relevant certificates that 
apply in each case. 

 

With transmitters for PROFIBUS PA and FOUNDATION 
Fieldbus H1 applications, FISCO interconnection methods can 
be used. 
 

3.3

 

Commissioning 

The commissioning and parameterization of the device may 
also be carried out in potentially explosive atmospheres using 
a handheld terminal that has been approved accordingly under 
consideration of an intrinsic safety installation check. 
Alternatively, an Ex modem can be connected to the circuit 
outside the potentially explosive atmosphere. 
 

3.4

 

Operating instructions 

3.4.1

 

Protection against electrostatic discharges 

The plastic parts inside the device can store electrostatic 
charges. 
Make sure that no electrostatic charges can accumulate when 
handling the device. 
 

 

 

A10096

A

B

+

-

+

-

Summary of Contents for TTH300 Series

Page 1: ...Operating Instruction OI TTH300 EN Rev D TTH300 Head mount temperature transmitter Measurement made easy...

Page 2: ...tion Additional documentation on TTH300 is available to download free of charge at www abb com temperature Alternatively scan this code Manufacturer ABB Automation Products GmbH Process Automation Sch...

Page 3: ...4 Returning devices 14 7 Installation 14 7 1 Installation options 14 7 1 1 Installation in the cover of the connection head 14 7 1 2 Installation on the measuring inset 15 7 1 3 Installation on the t...

Page 4: ...10 3 Possible HART error messages 38 10 4 Possible PROFIBUS PA and FOUNDATION Fieldbus error messages 39 11 Maintenance 40 11 1 Cleaning 40 12 Repair 40 12 1 Returning devices 40 13 Recycling and disp...

Page 5: ...ARNING indicates an imminent danger Failure to observe this information may result in death or severe injury CAUTION The signal word CAUTION indicates an imminent danger Failure to observe this inform...

Page 6: ...x certificate of conformity IECEx PTB 09 0014X Model TTH300 H1P and TTH300 H1F IECEx certificate of conformity IECEx PTB 11 0108X Ex ia IIC T6 Ex ia ib IIC T6 Ex iaD ib IIC T6 2 1 2 LCD indicators ATE...

Page 7: ...aximum permissible external inductance Lo 5 mH Maximum permissible external capacitance Co 1 4 F 2 3 2 LCD indicators Intrinsic safety type of protection Ex ia IIC Supply circuit Max voltage Ui 9 V Sh...

Page 8: ...room safe area Fig 1 A Transmitter B Supply isolator DCS input with supply Segment coupler Installation in a potentially explosive atmosphere Transmitters can be installed in all kinds of industrial s...

Page 9: ...ection standards The sensor can be installed in Zone 0 Zone 1 or Zone 20 ATEX Zone 2 Designation II 3 G Ex nA IIC T1 T6 Gc Ex area Zone 2 Safe area Fig 5 A Sensor B Transmitter in the housing with IP...

Page 10: ...R1P IS Model TTH300 R1F Control Drawing TTH300 R1F IS Class I Div 1 2 Groups A B C D Class I Zone 0 Ex ia Group IIC T6 CSA Non Incendive Model TTH300 R2H Control Drawing SAP_214824 Non Incendive SAP_2...

Page 11: ...les Proof of intrinsic safety is said to have been provided if the following conditions are fulfilled when a comparison is carried out in relation to the limit values of the equipment Transmitters int...

Page 12: ...sage is provided via the EDD or DTM or shown on the display The measured value remains available and maintenance measures can be taken at the same time 4 1 2 Sensor drift monitoring When two sensors a...

Page 13: ...ent temperature range on the name plate 10 refers only to the transmitter itself and not to the measuring element used in the measuring inset For devices with PROFIBUS PA or FOUNDATION Fieldbus the de...

Page 14: ...sport and storage Avoid storing the device in direct sunlight In principle the devices may be stored for an unlimited period However the warranty conditions stipulated in the order confirmation of the...

Page 15: ...the sensor in a housing that is suitable for the ambient conditions 7 2 Installing removing the optional LCD indicator Thanks to the LCD indicator interface the TTH300 can be operated using the LCD i...

Page 16: ...dangerous if touched or implement additional isolation measures for them Connections must only be established in a dead voltage state The transmitter has no switch off elements Therefore overcurrent...

Page 17: ...sistance thermometer RTD thermocouple combinations Fig 15 A 2 x voltage meter1 B 1 x voltage meter C 2 x Thermoelement1 D 1 x Thermoelement E 1 x RTD four wire circuit and 1 x Thermoelement1 F 1 x RTD...

Page 18: ...wire breakage Linear resistance measurement Sensor wire break Input thermocouples voltages Types B E J K N R S T in accordance with IEC 60584 U L in accordance with DIN 43710 C D in accordance with AS...

Page 19: ...emperature Analog Output optional HMI display Transducer Block 2 Discrete Input 1 enhanced diagnosis 1 Transducer Block 3 Discrete Input 2 enhanced diagnosis 2 Transducer Block 3 1 Sensor 1 sensor 2 o...

Page 20: ...ansmitter B Supply isolator PCS input with supply Segment coupler U1min Minimum supply voltage on the transmitter U2min Minimum supply voltage of the supply isolator DCS input R Line resistance betwee...

Reviews: