8.4.6. Electrical and mechanical accessories
- Make sure that the accessories are securely fi xed to the circuit-breaker.
- Make sure that the electrical accessories are correctly connected to the circuit-breaker.
- Gearmotor: after every 10000 operations, check the brushes for wear and replace the gearmotor if necessary.
- Make sure that the releases (YO, YU, YC) are in good conditions (absence of excessive wear, overheating, breakages) Fig. 28.
- Make sure that the mechanical operation counter functions correctly (if applicable) by operating the circuit-breaker.
2 Nm
Fig. 28
8.4.7. Protection
releases
- -Power the protection release with a PR030/B battery unit.
- Make sure that the protection release functions correctly: release test with the “Trip Test” (PR232, PR331, PR332) and “Autotest”
(PR332)
- With release PR332, make sure that the front leds or display do not indicate the presence of alarms.
- With release PR232 and PR331, make sure that the front leds do not indicate the presence of alarms.
- Make sure that the cables are correctly connected to the release modules and to the release itself (if applicable).
- Check the percentage of wear on the circuit-breaker contacts in PR332.
- Remove the PR030/B battery unit from the relay upon termination.
8.4.8.1 Test with SD Testbus2 (optional)
- Connect unit BT030 or BT030-USB to the relay that needs to be tested.
- Run the SD.TestBus2 program in a PC equipped with Bluetooth or Flash Drive connection, depending on the version of the
BT030 used.
- Once the connection between the relay and PC has been established, make sure that there are no alarm signals from the relay.
If this is the case, consult the ‘error messages’ and/or ‘troubleshooting’ sections of this manual.
- In normal operating conditions, proceed with the trip test and autotest (depending on the type of relay). For future check-outs,
you are advised to enter the current information in the area called User Data and/or Tag Name. These data will remain stored
in the relay itself.
- Remove the BT030 or BT030-USB fl ash drive from the relay.
8.4.8.2 Test with EKIP Connect (optional)
- Connect unit T&P unit to the relay that needs to be tested.
- Run the Ekip Connect program in a PC with fl ash drive connection.
- Once the connection between the relay and PC has been established, make sure that there are no alarm signals from the relay.
If this is the case, consult the ‘error messages’ and/or ‘troubleshooting’ sections of this manual.
- In normal operating conditions, proceed with the trip test and autotest (depending on the type of relay). For future check-outs,
you are advised to enter the current information in the area called User Data and/or Tag Name. These data will remain stored
in the relay itself.
- Remove the T&P cable from the relay.