4. Close the right door. Refer to section
5. Wait four hours.
The internal heater of the cabinet heats the inside of the cabinet and lets the
condensation evaporate.
6. Open the right door. Refer to section
7. Set the power module breakers to the on position.
a. Set the power module breakers from the
Off to the Manual position.
b. Set the power module breakers from the
Manual to the Auto position.
8. Close the right door. Refer to section
6.7
Local service portal operations
6.7.1
Start the local service portal
Preliminary requirements
•
The EVSE is ready for
operation. No charge
session is in progress.
•
Installation engineer
Procedure
1. Open the front door of the EVSE. Refer to section
.
The HMI starts the local service portal application. The outside HMI goes into
idle mode. On the inside HMI, the authorization screen shows.
2. Enter the pin code.
The PIN code is an alphanumeric code "1234WWYYSSS". The meaning of the
letters and numbers is:
•
1234: fixed code
•
WW: production week
•
YY: production year
•
SSS: serial number
3. Select
Continue.
6.7.2
Set the configuration parameters
1. Go to the configuration screen.
2. Wait for the system to load the data. This can take a few seconds.
3. Set
Authorization to ON or OFF. Use the toggle button.
4. Set the maximum AC input current in amperes.
The AC input current field has no maximum value. The correct AC input value is
the responsibility of the service engineer.
5. Save your changes.
6.7.3
Set the OCPP parameters
1. Go to the OCPP settings screen.
2. Wait for the system to load the data. This can take a few seconds.
Operation
9AKK108467A6997-EN | 003
41