Parameter
Specification
TN-C-S
TT (with upstream RCD)
Input voltage range
400 VAC +/- 10% (50 Hz or 60 Hz)
Power factor at full load
> 0.96
Efficiency
> 95% at nominal output power
Total harmonic distortion (current)
< 4.5%
10.15.2
AC input cable
Parameter
Specification
Cable shielding (optional)
If the local rules require shielded cables,
the cable shielding must be connected
to the PE rail at the two ends of the ca-
ble.
Diameter of the phase conductors
Refer to the local rules.
Diameter of the PE conductor
The same as the diameter of the phase
conductors
Surface
240 - 250 mm²
Diameter, including shielding
32 mm
Cable length (Terra 360)
L1/L2/L3: 210 mm (8.27 in)
If you use two cables per phase, make
sure that lugs are crimped in line with
the AC terminals (not twisted).
Cable lug
A60 - M12
10.15.3
Terra 360
Parameter
Specification [A]
Maximum rated input current
560
Maximum rated input current with AC
socket
590
Note: There are power limiting options available. Ask the manufacturer.
10.15.4
Terra 180
Parameter
Specification [A]
Maximum rated input current
280
Maximum rated input current with AC
socket
310
Note: Power limiting options are available. Ask the manufacturer.