TERRA DC WALLBOX
2023-06-20
17/39
3.2.5
Conduit for ethernet cable
The DC Wallbox does not have a hole designated for a conduit carrying only an ethernet cable to
connect to. If ethernet cable solution is required for an installation, please contact your ABB sales
contact person to review ethernet cable entry solutions.
3.2.6
Specification for ethernet cable
If the cellular connection is not available, ethernet connection must be made to the charger using a
shielded 8P+PE ethernet cable with RJ45 connectors. Additional recommendations include:
•
Maintain distance of 75 meters or less. Distances over 75 meters require a custom engi-
neered solution.
•
Minimum bandwidth:
upload: 128 kb/s
download: 4 Mb/s
•
99.9% availability
•
600V rated cable that may route beside input power wires for short distances
3.3
DC Wallbox placement
Placement of the Terra DC Wallbox must be carefully determined by accounting for charging cable
reach, DC Wallbox position with respect to parking space, bollards and wheel stops, ventilation and
working clearances, and other local codes and regulations (e.g. ADA requirements in the USA).
3.3.1
Charging cable reach
The Terra DC Wallbox charging cables are available in lengths of 3.5 or 7 meters. The charging ca-
bles exit the charger enclosure on both the right and left sides. The cables and the connectors
mounted on the cables are different depending on the charging standard and vary in flexibility.
The figure below shows an example of a dual connector charger with both types of connector and
the corresponding reach area. The green circle with a continuous line describes the CHAdeMO ca-
ble 3.5m and the red circle with a continuous line describes the CCS cable 3.5m. The broken lines
indicate the same cable types with a length of 7 meters (23 ft).