TERRA DC WALLBOX
2023-20-06
27/40
12.
Place the central cover on the unit and secure it in place by tightening the two screws located on the
left and right side of the cover. Center the bottom pins, rotate the cover, and tighten the 2 lateral
screws.
5.4.2
Install cable gland(s) or connect conduit to the unit.
The maximum diameter of the grid cable is 32 mm. The opening is pre-punched for a 1.25” trade size con-
duit. The minimum diameter of the grid cable is 22 mm with the standard fitted cable gland insert.
1. Slide the cable inside the grommets, ensure at least 10mm of cable external jacket inside the box (see
notes at the end of this section, before sliding the cable inside the grommet. Allow at least 24 inches of wire
from the conduit entry point to allow enough wire to route thru the internal grommet/cable glands and
wrap around to the terminal blocks.
Conduit Install shown as a comparison
208/240V 1-phase
version
Wire pass thru lo-
cations
Ferrite location