44 CI/FSV/FSS/430/450-EN Rev. G |
VortexMaster FSV430, FSV450 SwirlMaster FSS430, FSS450
Configuration of the alarm signaling via the current output
Not for devices with Modbus-communication!
Easy Setup
Iout at Alarm
High
Next
Edit
1. Use
to call up the edit mode.
2. Adjust the desired state in case of faults with
/
.
3. Confirm the selection with
.
Easy Setup
Easy Setup
High Alarm Value
Low Alarm Value
21.000 mA
3.600 mA
Next
Edit
Next
Edit
4. Use
to call up the edit mode.
5. Use
/
/
to set the alarm current.
6. Confirm the selection with
.
Zero point adjustment of the flowmeter
NOTICE
Prior to starting the zero point adjustment, make sure that:
— There is no flow through the sensor (close valves, shut-
off devices etc.).
— The sensor is completely filled with the medium to be
measured
Easy Setup
Auto Zero
Next
Edit
— Use
to start automatic adjustment of the zero point for
the system.
Configuration of the low flow cut-off
Easy Setup
Low Flow Cutoff
0.000 %
Next
Edit
1. Use
to call up the edit mode.
2. Use
/
/
to set the desired value for the low flow
cut-off.
3. Confirm the selection with
.
Menu
Easy Setup
Exit
Select
Once all parameter have been set, the main menu appears
again. The most important parameters are now set.
4. Use
to switch to the process display.