Installation instructions
Note: The circuit supplying mains power to the fitting must not be energised until installation of
the fitting is completed.
1.
Take out the cut-out template (348mm x 97mm) from the packing box; use a pencil to mark the cut-
out position on the ceiling. Once the ceiling cut-out is done, remove the face plate, recess the base
assembly through the ceiling cut-out (if access to the ceiling cavity is not available, connect the
mains power cord (active & neutral wire) and DALI control wires, secure with the cable ties
supplied, before recessing the base in the ceiling cut-out). Once recessed in the cut-out, tighten
the cam lock screws using suitable size Philips screwdriver or a power driven screwdriver set at
minimum torque, turning clockwise (refer figure 1), to secure the product to the ceiling.
2.
Once the base is secured to the ceiling, hold the diffuser assembly in your hand and connect the
diffuser wire loom polarised plug to the mother board (refer figure 3), the white wires on the plug
should be towards the centre of the fitting. Once the plug is connected, lay the wire loom carefully
inside the base and place one side of the diffuser in the diffuser holding latch hole and push up
the other side of the diffuser, the diffuser clicks and locks in place. Once the diffuser is locked in
place, the face plate is easily fixed to the base. Hold the face plate in your hand; make sure that
rectangular hole in the face plate for the LED and test switch lines up with LED and test switch in
the base. Bring up the face plate close to the base, place the locking tab on one side in the
position, the other end locking tab should line up on the correct position. Once both the locking
tabs are in the correct position, press gently, till it clicks and locks. Press gently in the middle to
lock middle 2 tabs, click sound indicates that tabs are locked in positon.
Removal instructions
1.
To remove/uninstall fitting from the ceiling,
the steps to be followed are the reversal of
installation process. Turn off mains power to
fitting, the fitting will automatically switch
into emergency mode as the mains power has
been turned off. It will stay on the emergency
mode until such time as the battery cut-off
threshold is reached.
2.
Remove face plate, gently insert a small
screwdriver into the first slot (first slot is
close to the diffuser end) and pull down
gently, repeat the same on the other end to
remove face plate.
3.
To remove diffuser assembly, hold the
diffuser holding latch with thumb on one end
and push gently to the opposite end to
remove diffuser from the holding latch. Once
diffuser is removed from the latch,
disconnect/remove wire loom plug from the
mother board. Once the diffuser assembly is
removed, disconnect the battery pack plug on
the mother board.
4.
Loosen the cam lock screws using suitable
size Philips screwdriver or a power driven
screwdriver set at minimum torque, turning
anti-clockwise. Once the cam lock screws are
loosened, the recessed base assembly can be
pulled down gently from the ceilng cut-out,
and disconnect the mains (active & neutral)
and DALI control wires from the ceiling.
5.
When the fitting is reconnected to the mains
supply, it will need time to recharge its
battery before it will be capable of a full
length discharge again. The ability of the
fitting to operate
on emergency is
determined by the
age, charge level,
operating
temperature
conditions and
environmental
circumstances of
the battery in the
fitting.
Important: 24 hours is required to allow the fitting battery to reach full capacity, ie: prior to a
discharge test. As the installer, it is your responsibility to conduct the initial discharge testing of
the installed fitting. Refer to AS/NZS 2293.
3.
Install the pictograph inserts by sliding into the diffuser. The pictograph inserts can be installed in
the diffuser prior to installing the diffuser assembly in the fitting. Fitting is supplied standard
with all pictograph insert options for single and double sided, as complete one box solution to
meet any site/project needs.
4.
The circuit supplying mains power to the fitting can now be energised.
5.
Check the operation of the fitting to ensure that the installation was successful. When powered
up, allow a few minutes to give the battery a small charge, then press the manual test button
located on the fitting. Hold the test button in for a few seconds and observe the operation of the
lamp switching from mains to the emergency mode. If the lamp on emergency mode works
momentarily, that’s okay. Try again in a few more minutes because if the battery was completely
discharged, it may take a little time to charge up enough to operate even momentarily. After this
time, press the test button again and if the lamp does not work at all, check the supply, the
connections and the troubleshooting guide at the end of this document.
Figure 2: Product installed in ceiling
Figure 1: Tight cam lock screw using Philips screwdriver
Mother board
Diffuser
holding
latch
White
wires
Figure 3: Connect wire loom plug to the mother board
Figure 4