background image

SREA-01 Quick Start-up Guide

3

3. Connecting drive(s)

If you have a single ACS350, ACH550 or ACS550, it is easiest to 
use the supplied RJ45 cable to connect to the panel port. 

If you have multiple drives or an ACS800, use the RS-485 
connection. Connect the A- channels of the SREA-01 unit and the 
drives together, the B+ channels together and the COM connector 
to the data ground connectors of the drives. Use 120 ohm 
terminating resistors in the network.

4. Basic drive settings

Check the communication settings of the drive (either group 52 or 
53 in most drives, depending on the connection type).

Station id/number has to be unique for each drive! The baud rate 
selection and parity have to be same on all drives and
SREA-01. You can use for example 9600 bit/s, no parity, 1 stop bit. 

5. Basic SREA-01 settings 

You can change the Ethernet settings under 

Setup – Ethernet

Select the correct drive connection settings under 

Setup – 

Modbus

.

• Select Physical Interface.

• Usually most other settings are suitable by default (RTU, 

9600 bps, no parity, 1 stop bit).

SREA-01

X1 pin

Wire

Panel port

RJ45 pin

RX (RS-232)

white-orange

1

TX (RS-232)

white-blue

3

COM

orange and blue

2 and 6

X1 RS-232:

Select EIA-232

X1 RS-485:

Select EIA-485

X2:

Select EIA-232 D-sub

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]