34
2TLC010073M0201 Rev.G
CH1
Mode
CH2
Status
Action
green
flash blue
off
CH1 accepted and
CH2 unaccepted,
a timer function is
counting down
while remaining
inactivated
red
fast flash blue
red
Fail-safe mode, a
new setting has
been stored
Power cycle the
unit to use the
stored setting
red
flash red
red
Fail-safe mode,
the system is
waiting for a new
setting
Enter and store a
new setting
red
fast flash red
red
The safety relay is
in failsafe mode
Check error codes
and installation
red
fast flash red
fast flash red
Failsafe mode due
to short-circuit
between CH2 and
24 VDC or T1
Check error code.
Check and
remove the short-
circuit
10.3
Display codes
Display indication
Status message
8.8.8.
The safety relay is powering up. The segments
on the display are shortly lit up during the
powering up process
E.xx
Error code. The error code E.xx is flashing if an
error is present
Error code
Error type
Procedure for correction
E.10 – E.14
Internal error
1. Power cycle the safety relay
2. If the error code remains,
contact your ABB
representative.
E.15
Relay hardware error
1. Power cycle the safety relay
2. If the error code remains,
contact your ABB
representative.
E.16
+24 V power error
Check the supply voltage
E.20 – E.26
Input/Output (I/O) error
1. Power cycle the safety relay
2. If the error code remains,
contact your ABB
representative.
E.30 – E.34
System error
1. Power cycle the safety relay
2. If the error code remains,
contact your ABB
representative.
E.50
Internal error
1. Power cycle the safety relay
2. If the error code remains,
contact your ABB
representative.