Configuration with TTH300 transmitters
SM/TSP/SIL-EN SensyTemp
TSP
13
Warning!
Inspections:
Write protection must be checked as follows:
1. Lock via HMI (human-machine interface):
- Check whether the lock icon is displayed on the LCD display.
- Select the menu item “Fault Signaling” and make sure the edit icon is not displayed on
the LCD display.
- Press the Edit button to make sure that there is no response on the LCD display.
2. Lock via DTM:
- HMI available: Check whether described under item 1.
- No HMI available (check the write protection):
Go to <Device>,<Parametrize> Current Output / Damping and update the damping
value. Select “Save Device Data in Device” and check whether the message "Device is
write-protected" is displayed.
Warning!
The software write protection does not lock again automatically. It remains unlocked until it is
reset.
Diagnostic Setup
The diagnostic setup of the device meets safety requirements and includes the following error
detections:
•
Sensorboard communication error
•
Sensorboard error
•
Sensorboard A/D converter error
•
Measuring error device temperature
•
Sensor limit value alarm upper and lower
•
Sensor error Ch. 1 and Ch. 2
•
Sensor configuration RTD,R with 2, 3, 4-wire breakage and short circuit
•
Sensor configuration TC, mV with wire break
•
Redundancy-Mode Ch1 and Ch2 with enabled drift, drift monitoring
Summary of Contents for SensyTemp TSA101
Page 16: ...Safety engineering parameters 16 SensyTemp TSP SM TSP SIL EN ...
Page 18: ...Management Summary FMEDA 18 SensyTemp TSP SM TSP SIL EN 12 Management Summary FMEDA ...
Page 19: ...Management Summary FMEDA SM TSP SIL EN SensyTemp TSP 19 ...
Page 20: ...Management Summary FMEDA 20 SensyTemp TSP SM TSP SIL EN ...
Page 21: ...Management Summary FMEDA SM TSP SIL EN SensyTemp TSP 21 ...