1MRK 511 434-UEN A
Section 5
SAM600 System Startup
SAM600 Process Bus I/O System
45
Operation Manual
Section 5
SAM600 System Startup
5.1
Start-up behavior
SAM600 modules ship with factory default settings. All settings are at their default
values (see table
Parameter settings
in the SAM600 engineering manual for default
value of each settable parameter). In factory default settings, SAM600 modules do
not send any sampled value streams to any port. The HMI flashes to indicate the
Wait for Configuration
state.
The user has to create a configuration for the SAM600 system, and write the
configuration to the SAM600 modules in order to switch on their sampling and
merging functionality. The process for creating and downloading a configuration is
described in the SAM600 Engineering Manual (1MRK 511 433-UEN).
In factory default settings, SAM600 modules do not publish
sampled value streams.
Inappropriate settings on the SAM600 modules may lead to
misbehavior in protection and control applications due to wrong
information transmitted in the IEC/UCA 61850-9-2LE sampled
value streams.
Before powering on a SAM600 module, check the firm wiring of
analog and digital inputs. Verify firm grounding of SAM600
modules.
SAM600 modules will restart once the configuration is applied, activate all
parameter settings, port configurations and SV configurations which are contained
in the configuration and then start-up the SAM600 sampling and merging
functionality. Steady light of the HMI indicates the
Normal Operation
state. A new
configuration is subject to verification against the physical SAM600 system
topology, see
Section
If a configuration has been downloaded to a SAM600 module, the same
configuration is applied each time the SAM600 module starts up.
If the command
Reset to factory default
is applied then the SAM600
module will be reset to its factory defaults and it will restart into the
Wait for Configuration
state as described above.