STEP 7 Continued


Figure 7a. Installation of breaker


Figure 7b. Installation of breaker

8

9

6x 6x

6

13

7

4x

4x

2x

1x

1x 15

Remove knock out features before 
assembly to breaker

Remove knock out features before 
assembly to breaker

14

!

!

3

STEP 7

Install the pre-assembled breaker. Attach the breaker assembly to 

mounting brackets [4] with mounting stud [6], torque the mount

-

ing stud [6] to 18 lb-in. Refer figure 7a. Attach to link assembly with 

Hex terminal screw [8] and conical washer [9], torque the screw [8] 
to specification in document 1SDH002011A1002. Refer figure 7b.  

STEP 9
Note: Use M3 x 8 if the required screw is not available.

   

 

Install the phase barrier [13] on the breaker with Pan head, Phillips 
screw [7], torque the screw [7] to 9 lb-in. Refer figure 9.

STEP 8

Remove the plastic wall (knock out) in terminal cover and install the  
terminal cover on load side (slide down in as shown in figure 8).

Figure 9. Installation of phase barrier


Figure 8. Installation of terminal cover

STEP 11

Prepare the filler plates [14, 15] if single breaker installation is used. 

Attach the blankout out plate [17] to the filler plate with thread 

forming screw [5], torque the screw [5] to 30 lb-in. Refer figure 11.

Figure 11. Preparation of filler plate


Figure 10. Tighten the bolted strap connection

STEP 10

Tighten all the three bolted strap connections (carriage bolt as-
sembly) at the vertical bus to 65 lb-in. It may be necessary to re-
move adjacent circuit breaker modules to allow access to the 
bolted connections at the vertical bus.

Item 5 - screw to be assembled with screw 

head from rear/behind the filler plate and 

thread end projecting outside as shown 

17

5