background image

STEP 2

Find the side of the panel interior at which the dimension from the 
face of nearest vertical bus to the inner face of the bus support rail 

is 2.75 inches, as illustrated in figure 2 .

Main Bus

Lugs installed 
on load side

LOAD

LOAD

LINE

LINE

2.75" REF

Figure 2. Double branch, ABB XT5; Assembly end view


Figure 3. Installation of right link assembly


Figure 4. Installation of middle link assembly


Figure 1. Breaker preparation

Right side 
cable  entry

Left side 
cable  entry

1

11

12

1

2.75"

REF

2

3

2

3

2x 2x 2x

2x 2x 2x

STEP 6

Install the breaker mounting bracket [4] on the bus support rail 

with the thread forming screw [5], torque the screw to 30 lb-in. 

Refer figure 6.


Figure 5. Installation of left link assembly


Figure 6. Installation of breaker mounting bracket

10

1

5

4

2

3

2x

4x

2x 2x 2x

!

2

STEP 1

Prepare the breaker, refer to breaker instruction document for 

more information. Install the appropriate lugs as in load side as 
shown in figure 1.

Step 3

Install the link assembly - Right link assembly [12] to adjacent pole 
from 2.75 inches ref. as shown in figure 3. Fasten the complete link 

assembly loosely to the vertical bus with carriage bolt [1], Belleville 

washer [2] and nut [3]. Refer figure 3.

Step 4

Install the link assembly - Middle link assembly [11] to middle pole 
as shown in figure 4. Fasten the complete link assembly loosely to 

the vertical bus with carriage bolt [1], Belleville washer [2] and nut 

[3]. Refer figure 4.

Step 5

Install the link assembly - Left link assembly [10] to outermost pole 
as shown in figure 5. Fasten the complete link assembly loosely to 

the vertical bus with carriage bolt [1], Belleville washer [2] and nut 

[3]. Refer figure 5.