ABB | SACE Emax 2
10 | © 2018 ABB | 1SDH001316R0002 - ECN000086018 - Rev. C
Ekip Touch protection trip unit | 4 - Setting the parameters
4 - Setting the parameters
Modifying a parameter
To set a parameter, you need to select it. Selecting a parameter opens the page
Modify Parameter
.
There are two possible types of
Modify Parameter
page:
• By option: it consists of a list of the values that can be assigned to the parameter.
• By value: graphical page with a bar for assigning the parameter a numerical value within a range..
Programming the trip unit
When a parameter is modified, the new value is indicated in the Start menu, and the parameter is associated
to a tick symbol.
The menu with submenus and parameters with ticks appears as follows:
S(V) Protection
Enable
On
Trip enable
On
Function
Step mode
I20 Threshold
0.60In (240A)
Ul Threshold
100% Un (100V)
Figure 6
The ticks indicate that the changes are not effective. In order make a change effective, the trip unit must be
programmed. To program the trip unit, you need to press the key
HOME
, that opens the page
Programming
.
Alternatively, you can go up to the higher level menus until the page is displayed.
In the page
Programming
:
• A list of the changes made is displayed.