![ABB SACE Emax 2 E6.2 Instruction Handbook Manual Download Page 58](http://html.mh-extra.com/html/abb/sace-emax-2-e6-2/sace-emax-2-e6-2_instruction-handbook-manual_3045203058.webp)
58
INSTRUCTION HANDBOOK
UL version - Current rating up to 5000A
Tools
Torx key
219
By means of the torx key (size 15) unscrew the
10 screws fixing the claw contacts to the pole.
221
Manually remove the spacers located below the
claw contacts.
222
By means of the torx key (size 40) unscrew
the 6 screws fixing the terminals and their
protections to the pole.
220
Push the claw contacts as indicated by the
arrows and after manually remove the claw
contacts.
Circuit breakers in UL version characterized by a current rating up to 5000A show differences
at level of parts involved in this disassembly phase, consequently here below an analogous
section is provided for these circuit breakers.
No. 15
No. 40