Section 3 Run-time Operation
CI840
3BSE027630-600 B
57
within the defined time, the channels on the output modules are set to the
predefined value (OSP value).
•
HCIR Enable
Hot Configuration In Run active
•
HCIR Factor
Hot Configuration In Run Factor
•
HCIR Watchdog
Hot configuration In Run Worst Case Bus Cycle Base
Configuration Control of DI825/DI830/DI831/DI885 with CI840 for SOE
To use the modules DI825/DI830/DI831/DI885 for SOE, open the
ServiceEntries.xml
file, and set the value of the ‘EnableSOE’ attribute to 1.
The location of
ServiceEntries.xml
is
<ProgramData>\ABB\800xA\S800DTM. The ProgramData folder is hidden, by
default.
describes the different configuration control options for the SOE supported
modules DI825, DI830/DI831 and DI885, used with CI840 for AC870P.
It is assumed that the EnableSOE attribute is set to 1 globally.
Table 4. Configuration control of SOE supported modules used with CI840, for
AC870P
Status of ‘Sequence of
Events’ checkbox in
CI840 Configuration
Control
Displayed status in the
‘SOE’ drop-down menu in
DI825/DI830/DI835/DI885
Configuration Control
Whether the displayed
SOE status in DI8xx
can be changed
Unchecked, by default,
after inserting the CI840
for the first time
SOE disable
No
Checked after an
unchecked status
SOE disable
Yes
Summary of Contents for S800 I/O
Page 1: ...Power and productivity for a better world S800 I O DTM 6 0 System Version 6 0 ...
Page 2: ......
Page 3: ...S800 I O DTM 6 0 ...
Page 20: ...Intended User Section 1 Introduction 20 3BSE027630 600 B ...
Page 28: ...Initial Installation Section 2 Installation 28 3BSE027630 600 B ...
Page 172: ...DP840 Dynamic values Appendix B Dynamic Data 172 3BSE027630 600 B ...
Page 174: ...Updates in Revision Index B 174 3BSE027630 600 B ...
Page 175: ......