QUICK START GUIDE
Information
-
External electrical equipment
This equipment includes an embedded DC output surge protection network to mitigate risk of damage to itself
from external transient events occurring on the DC output conductors. This device is not intended to be used as a
surge suppression device for the externally connected devices being powered by the unit. Connected devices must
provide their own suitable DC input transient suppression as dictated by the equipment
’
s vendor for the
installation site environment or per company or industry standards (e.g., ITU K series standards).
Information
-
Lifting the unit
The rectifier assembly is less than 80 lbs. and should have two installers to place the unit into position to the pole
or wall mounting bracket.
Information
-
External icing
When external icing affects the access to the four hardware screws a plastic or rubber hammer can be used to
break the ICE to remove the securing screws.
Information
-
For Replacement applications
1.
Unlock and open door of unit.
2.
Turn mains breaker feeding the unit following Lock
-
Out Tag
-
Out procedures.
Warning
: Line side of Mains breaker is still energized high voltage.
3.
Remove power from source feeding mains breaker in the unit by following local regulatory and National Electric
Code (NEC) practices to deenergize power from the AC meter
4.
with a meter, confirm the AC input and DC outputs are all deenergized.
5.
Remove the dead
-
front covers and disconnect wiring
6.
Secure all wiring.
7.
Remove straps holding the unit in position.
8.
Remove the pole mounted unit.
9.
Install the replacement unit and secure with the appropriate mounting straps.
10.
Install the electrical and dc output following removal using the installation procedure described earlier in this
document.
11.
Close all openings and power the input and verify the LED is now green.
12.
Reinstall both dead
-
front covers and close and lock front door.
Information
-
Touch up paint
Should any part of the unit coating be damaged, repaint using:
LVP Powder and Paints
RAL7035 Touch Up Paint
-
Light Grey
-
12 oz Spray Can.