ABB Substation Automation
Products and Systems
User’s Guide
REU 513
28
1MRS750886-MUM
Note!
Only the indication for the latest start or trip situation remains active as defined in
settings. Each indication is overridden by a newer indication of higher priority.
Table 7: SGF3
Switch
Function
Default
setting
SGF3/1
The operation mode for the start indicator of stage U>.
• 0 = The start indicator automatically resets once the fault
disappears.
• 1 = The start indication remains even if the fault disappears.
0
SGF3/2
The operation mode for the trip indicator of stage U>.
• 0 = The trip indicator automatically resets once the fault
disappears.
• 1 = The trip indication remains even if the fault disappears.
1
SGF3/3
The operation mode for the start indicator of stage U>>.
• 0 = The start indicator automatically resets once the fault
disappears.
• 1 = The start indication remains even if the fault disappears.
0
SGF3/4
The operation mode for the trip indicator of stage U>>.
• 0 = The trip indicator automatically resets once the fault
disappears.
• 1 = The trip indication remains even if the fault disappears.
1
SGF3/5
The operation mode for the start indicator of stage U<.
• 0 = The start indicator automatically resets once the fault
disappears.
• 1 = The start indication remains even if the fault disappears.
0
SGF3/6
The operation mode for the trip indicator of stage U<.
• 0 = The trip indicator automatically resets once the fault
disappears.
• 1 = The trip indication remains even if the fault disappears.
1
SGF3/7
The operation mode for the start indicator of stage U<<.
• 0 = The start indicator automatically resets once the fault
disappears.
• 1 = The start indication remains even if the fault disappears.
0
SGF3/8
The operation mode for the trip indicator of stage U<<.
• 0 = The trip indicator automatically resets once the fault
disappears.
• 1 = The trip indication remains even if the fault disappears.
1
Σ
SGF3
170