Name
Values (Range)
Unit
Step
Default
Description
OscillationTime6
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 6
Threshold7
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 7
DebounceTime7
0.000 - 0.100
s
0.001
0.005
Debounce time for input 7
OscillationCount7
0 - 255
-
1
0
Oscillation count for input 7
OscillationTime7
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 7
Threshold8
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 8
DebounceTime8
0.000 - 0.100
s
0.001
0.005
Debounce time for input 8
OscillationCount8
0 - 255
-
1
0
Oscillation count for input 8
OscillationTime8
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 8
Threshold9
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 9
DebounceTime9
0.000 - 0.100
s
0.001
0.005
Debounce time for input 9
OscillationCount9
0 - 255
-
1
0
Oscillation count for input 9
OscillationTime9
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 9
4.1.3.2
Setting parameters for communication module
Table 10:
COM05_12BI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
BatteryVoltage
24 - 250
V
1
110
Station battery voltage
Table 11:
COM05_12BI Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Threshold1
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 1
DebounceTime1
0.000 - 0.100
s
0.001
0.005
Debounce time for input 1
OscillationCount1
0 - 255
-
1
0
Oscillation count for input 1
OscillationTime1
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 1
Threshold2
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 2
DebounceTime2
0.000 - 0.100
s
0.001
0.005
Debounce time for input 2
OscillationCount2
0 - 255
-
1
0
Oscillation count for input 2
OscillationTime2
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 2
Threshold3
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 3
DebounceTime3
0.000 - 0.100
s
0.001
0.005
Debounce time for input 3
OscillationCount3
0 - 255
-
1
0
Oscillation count for input 3
OscillationTime3
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 3
Table continues on next page
1MRK 504 135-UEN A
Section 4
Binary input and output modules
53
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...