8.4.6
Monitored data
Table 89:
EF4PTOC Monitored data
Name
Type
Values (Range)
Unit
Description
STDIR
INTEGER
3=Both
1=Forward
2=Reverse
0=No direction
-
Fault direction coded as
integer
IOp
REAL
-
A
Operating current level
UPol
REAL
-
kV
Polarizing voltage level
IPol
REAL
-
A
Polarizing current level
UPOLIANG
REAL
-
deg
Angle between polarizing
voltage and operating
current
IPOLIANG
REAL
-
deg
Angle between polarizing
current and operating
current
IOPDIR
REAL
-
A
Amplitude of the
directional operating
quantity
8.4.7
Operation principle
Four step residual overcurrent protection, zero or negative sequence direction
EF4PTOC function has the following four “Analog Inputs” on its function block in the
configuration tool:
1. I3P, input used for “Operating Quantity”.
2. U3P, input used for “Voltage Polarizing Quantity”.
3. I3PPOL, input used for “Current Polarizing Quantity”.
4. I3PDIR, input used for “Operating Directional Quantity”.
These inputs are connected from the corresponding pre-processing function blocks in
the Configuration Tool within PCM600.
8.4.7.1
Operating quantity within the function
If the function is set to measure zero sequence, it uses Residual Current (3I
0
) for its
operating quantity. The residual current can be:
1. directly measured (when a dedicated CT input of the IED is connected in
PCM600 to the fourth analog input of the pre-processing block connected to
EF4PTOC function input I3P). This dedicated IED CT input can be for example,
connected to:
Section 8
1MRK 504 135-UEN A
Current protection
160
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...