Table 10: Digital inputs
Power supply version
PS1/240 V (High) PS1/240 V (Medium),
PS2/240 V
PS1/48 V (Low),
PS2/48V
Input voltage, dc
220 V
110/125/220 V
24/48/60/110/125/
220 V
Nominal treshold voltage, dc
- operating range, dc
155 V
155…265 V
80 V
80...265 V
18 V
18...265 V
Current drain
~2…25 mA
Power consumption/input
<0.8 W
Pulse counting (specific digital inputs),
frequency range
0…100 Hz
Time synchronization (specific digital
inputs) synchronization rate
once per minute or once per second
Table 11: RTD/analog inputs
Supported RTD sensors
100
Platinum
TCR 0.00385 (DIN 43760)
250
Platinum
TCR 0.00385
1000
Platinum
TCR 0.00385
100
Nickel
TCR 0.00618 (DIN 43760)
120
Nickel
TCR 0.00618
250
Nickel
TCR 0.00618
1000
Nickel
TCR 0.00618
10
Copper
TCR 0.00427
120
Nickel
TCR 0.00672 (MIL-T-24388C)
Max lead resistance
(three-wire measurement)
200
per lead
Accuracy
±0.5% of full scale
±1.0% of full scale for 10
Copper RTD
Isolation
2 kV (inputs to outputs and inputs to protective earth)
Sampling frequency
5 Hz
Response time
Filter time + 30 ms (430 ms...5.03 s)
RTD/ Resistance sensing
current
max 4.2 mA RMS
6.2 mA RMS for 10
Copper
Current input impedance 274
±0.1%
Table 12: Analog outputs
Output range
0...20 mA
Accuracy
±0.5% of full scale
Max load
600
Isolation
2 kV (output to output, output to inputs and output to
protective earth)
Response time
85 ms
Transformer Terminal
RET 541, RET 543, RET 545
1MRS755543
33
Table 13: Signal outputs
Max system voltage
250 V ac/dc
Continuous carry
5 A
Make and carry for 0.5 s
10 A
Make and carry for 3 s
8 A
Breaking capacity when control circuit time-constant
L/R <40 ms, at 48/110/220 V dc
1 A/0.25 A/0.15 A