background image

Section 3

1MAC306892-MB C

Vendor-specific implementation

 22

RER620

Communication Protocol Manual

3.6.17

OvInd NoGI IOA

• Min: 0
• Max: 255/65535/16777215
• Default: 60000

The protective relay generates an overflow indication event with this address if the lost 
event is  not included in any of the interrogation groups. Based on this information, the 
client knows that the interrogation is not needed because the missed data is not updated 
anyway.

• If 

OvInd NoGI IOA

 is set to zero, the overflow indication is disabled for the points 

that are not part of some interrogation groups.

• If 

OvInd NoGI IOA

 is set to same value as 

OvInd IOA

, only one indication event is 

generated regardless whether the point is included in the interrogation group or not.

• The maximum value depends on the IOA length setting.

3.6.18

Event order

• Accurate time (default)
• Preserve chronology

The protective relay has accurate time stamps for every data attribute which is part of an 
IEC 61850 dataset. Most of them are updated in a chronological manner. However, there 
may be some special data items that do not have system-level timestamp available, such 
as circuit breaker control return indication. If the client needs strictly chronological event 
buffering, 

Event order

 should be set to "Preserve chronology". If the events are collected 

to a SCADA system, which is able to buffer and sort the received events at the system 
level, it is recommended to use "Accurate time" instead.

3.6.19

Selection time-out

• Min: 1
• Max: 65
• Default: 30
• Unit: seconds

This is the maximum time between the Select and Execute commands for the circuit 
breaker controlling in the select-before-operate mode. The controllable object's IEC 
61850-level 

Selection time-out 

parameter is not used when the control is made by the IEC 

60870-5-101/104 client.

Applicable only if Overflow mode is set to "Indication".

Summary of Contents for Rellon 620 Series

Page 1: ...Relion 620 series RER620 IEC 60870 5 101 104 Communication Protocol Manual ...

Page 2: ......

Page 3: ...Document ID 1MAC306892 MB Issued 07 20 2017 Revision C Product version 1 3 Copyright 2017 ABB All rights reserved ...

Page 4: ...losed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of ABB Group All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders Warranty Please inquire about the terms of warranty from your nearest ABB representative ABB Inc Distribution Automation 4300 Coral Ridge Drive Cora...

Page 5: ...product failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipment and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks This document has been carefully checked by ABB but deviations cannot be compl...

Page 6: ...g electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255 26 for the directive and with the product standards EN 60255 6 and EN 60255 27 for the directive The protective relay is designed in accordance with the international standards of the I...

Page 7: ... application functions 10 Data acquisition 10 Event acquisition 11 Interrogation 11 Clock synchronization 11 Command transmission 11 Changes in protocol and link parameters 12 Acquisition of transmission delay 12 Analog Value Deadband 12 Section 3 Vendor specific implementation 13 615 620 series implementation 13 Internal IEC 61850 data modeling 13 Instances 13 Selecting between IEC 60870 5 101 an...

Page 8: ...9 OA length 19 Link address length 19 ASDU address length 19 Single character response 20 Show bad time 20 Time format 20 Event time 21 Overflow mode 21 OvInd IOA 21 OvInd NoGI IOA 21 Event order 22 Selection time out 22 Cyclical period 22 Transmit window 23 Receive window 23 Transmit timeout 23 Receive timeout 23 Link test interval 24 Diagnostics 24 Status 24 Received frames 24 Transmitted frames...

Page 9: ...1MAC306892 MB C Section RER620 3 Communication Protocol Manual Section 5 Glossary 31 ...

Page 10: ...Section 1MAC306892 MB C 4 RER620 Communication Protocol Manual ...

Page 11: ...es on vendor specific implementations 1 2 Intended audience This manual addresses the communication system engineer or system integrator responsible for pre engineering and engineering for communication setup in a substation from a protective relay perspective The system engineer or system integrator must have a basic knowledge of communication in protection and control systems and thorough knowle...

Page 12: ...lled The operation manual contains instructions on how to operate the protective relay once it has been commissioned The manual provides instructions for monitoring controlling and setting the protective relay The manual also describes how to identify disturbances and how to view calculated and measured power grid data to determine the cause of a fault The application manual contains application d...

Page 13: ...te http www abb com substationautomation 1 4 Symbols and conventions 1 4 1 Safety indication symbols Although warning hazards are related to personal injury it should be understood that operation of damaged equipment could under certain operational conditions result in Document revision date Product version History A 11 23 2010 1 0 First release B 10 31 2011 1 1 Content updated to correspond to th...

Page 14: ...for example To navigate between the options use and HMI menu paths are presented in bold for example Select Main Menu Settings LHMI messages are shown in Courier font for example To save the changes in non volatile memory select Yes and press Parameter names are shown in italics for example The function can be enabled and disabled with the Operation setting Parameter values are indicated with quot...

Page 15: ...ment of basic application functions Link layer defines the frame formats and the transmission procedures of the IEC communication Physical layer defines the hardware dependent specifications of the IEC 60870 5 101 IEC 60870 5 104 communication interfaces 2 2 Transmission IEC 60870 5 101 allows two alternative transmission procedures unbalanced and balanced to be used in the communication between t...

Page 16: ...ONFIRM and SEND NO REPLY transmission services The SEND NO REPLY transmission service can be initiated only by a controlling station with a broadcast address in a multiple point to point configuration 2 3 Basic application functions 2 3 1 Data acquisition The data delivered by a controlled outstation can be replies to commands or process values which are collected cyclically upon change or upon re...

Page 17: ...roups at once general 2 3 4 Clock synchronization The clock of the controlled outstation has to be synchronized with the clock of the controlling station Synchronizing of the clocks provides a correct chronological sequence of time tagged events or information objects that are transmitted to the controlling station or that are logged locally After system initialization the clocks are initially syn...

Page 18: ...rotocol and link parameters are changed the new values take effect after they have been committed 2 3 7 Acquisition of transmission delay The value of time correction is determined by the sum of the transmission delay and the internal equipment delay The transmission delay is a value which can be acquired either separately by parameterization or via a dynamic procedure initiated by the controlling...

Page 19: ...tly managed For example if a client is not available for event receiving that does not affect the data buffering for other clients Every instance has independent configuration and data object mapping It is possible to build a configuration where the amount of information objects is different for the clients For example a client with slow connection gets only the most important data 3 1 3 Selecting...

Page 20: ...alanced Otherwise no change is needed COT Length Usually set to 1 This setting must have the same value in the master and slave devices IOA Length Usually set to 2 This setting must have the same value in the master and slave devices Link Address Length Usually set to 1 This setting must have the same value in the master and slave devices ASDU Address Length Usually set to 1 This setting must have...

Page 21: ...dling 3 3 1 Overflow mode The protocol instance can be configured to keep either the newest or the oldest events in case of buffer overflow The event buffer overflows typically in a situation where a lot of signals change at the same time and the client is not able to fetch all the event reports quickly enough In these cases the events that occurred in that critical moment are the most important I...

Page 22: ...nsmitted in primary units such as A V or Hz The scaling is based on the measuring transformer ratio 3 4 3 Control objects CSC CDC Two types of control objects are available The double bit controls are employed for circuit breaker control points The C_DC_XX 46 59 type commands should be issued to control the double bit points The single bit controls are used for all the other control points e g set...

Page 23: ... the different information object types 3 5 2 Configuring communication options Configure the communication options by using LHMI or PCM600 to set the parameters in Configuration Communication IEC60870 5 101 104 For remapping the data object use the Communication Management tool in PCM600 3 6 Communication parameters 3 6 1 Port NONE default IEC101 COM1 IEC101 COM2 IEC104 Ethernet The setting enabl...

Page 24: ...01 frame If this setting is too low the protective relay may interpret incoming message as multiple frames which causes discarding of the frame If the link uses for example radio modem it might be needed to adjust the End delay setting to a higher value The delay time is defined in characters at the current baud rate 3 6 4 Device address Min 1 Max 255 65535 Default 1 The Device address is the iden...

Page 25: ... are 1 for IEC 60870 5 101 and 2 for IEC 60870 5 104 3 6 8 OA length Min 1 Max 3 Default 2 Unit bytes For the communication frames the information object address IOA length is configurable and should be set to the same value throughout the network Typical values are 2 for IEC 60870 5 101 and 3 for IEC 60870 5 104 3 6 9 Link address length Min 1 Max 2 Default 1 Unit bytes In a communication frame t...

Page 26: ...2 Show bad time Enabled default Disabled If the protective relay time is not synchronized properly the time quality is marked as bad or inaccurate The time quality is indicated as a flag in the changed data report If Show bad time is set to Disabled the protective relay does not indicate the bad time flag which may be useful in some systems If the time quality indication is disabled the client is ...

Page 27: ...t case the oldest events in the buffer are discarded 3 6 16 OvInd IOA Min 0 Max 255 65535 16777215 Default 60000 The protective relay generates an overflow indication event with this address if the lost event is included in any of the interrogation groups Based on this information the client requests for interrogation to get the latest momentary values If OvInd IOA is set to 0 the overflow indicat...

Page 28: ... time default Preserve chronology The protective relay has accurate time stamps for every data attribute which is part of an IEC 61850 dataset Most of them are updated in a chronological manner However there may be some special data items that do not have system level timestamp available such as circuit breaker control return indication If the client needs strictly chronological event buffering Ev...

Page 29: ...at a given time The transmitter stops the transmission at k unacknowledged I format APDUs 3 6 22 Receive window Min 1 Max 32767 Default 8 Unit APDU The receiver acknowledges at the latest after receiving w I format APDUs Recommendation w should not exceed two thirds of k 3 6 23 Transmit timeout Min 1000 Max 255000 Default 15000 Unit ms t1 is the timeout of a sent U frame or I frame t1 starts after...

Page 30: ...fied period of time in which no data transfers occur time out The reception of every frame I frame S frame or U frame retriggers timer t3 The accuracy for t3 is 1 second The timeout setting should be set as a multiple of 1000ms 3 7 Diagnostics All of the counters with the exception of the Status point show value 1 when no connection is established after the protective relay restart 3 7 1 Status Th...

Page 31: ...ted errors on the physical layer since last the startup or a diagnostic reset 3 7 5 Link errors The Link errors counter shows the number of detected errors on the link layer since the last startup or a diagnostic reset 3 7 6 Transport errors The Transport errors counter shows the number of detected errors on the transport layer since the last startup or a diagnostic reset ...

Page 32: ...Section 3 1MAC306892 MB C Vendor specific implementation 26 RER620 Communication Protocol Manual ...

Page 33: ... mode setting for instance 1 COT Length 1 1 2 1 Cause of transmission length IOA Length 1 1 3 2 Information object address length Link Address Length 1 1 2 1 Link address length ASDU Address Length 1 1 2 1 ASDU address length Single Char Resp 1 0 Disabled 1 Enabled 0 Disabled Single character response enabled disabled Show Bad Time 1 0 Disabled 1 Enabled 1 Enabled Enable disable bad time quality i...

Page 34: ...s of the instance 2 Link Mode 2 0 Balanced 1 Unbalanced 0 Balanced Link mode setting for instance 2 COT Length 2 1 2 1 Cause of transmission length IOA Length 2 1 3 2 Information object address length Link Address Length 2 1 2 1 Link address length ASDU Address Length 2 1 2 1 ASDU address length Single Char Resp 2 0 Disabled 1 Enabled 0 Disabled Single character response enabled disabled Show Bad ...

Page 35: ...tion Name Type Values range Unit Description Status 1 BOOLEAN 0 False 1 True Status Received frames 1 INT32 1 2147483646 Received frames Transmitted frames 1 INT32 1 2147483646 Transmitted frames Physical errors 1 INT32 1 2147483646 Physical layer errors Link errors 1 INT32 1 2147483646 Link layer errors Transport errors 1 INT32 1 2147483646 Transport layer errors Status 2 BOOLEAN 0 False 1 True S...

Page 36: ...Section 4 1MAC306892 MB C IEC 60870 5 101 and IEC 60870 5 104 parameters 30 RER620 Communication Protocol Manual ...

Page 37: ...ibility EPA Enhanced performance architecture Ethernet A standard for connecting a family of frame based computer networking technologies into a LAN HMI Human machine interface IEC 60870 5 IEC standard for telecontrol equipment and systems Part 5 defines transmission protocols IEC 60870 5 101 Companion standard for basic telecontrol tasks IEC 60870 5 104 Network access for IEC 60870 5 101 IEC 6185...

Page 38: ...Section 5 1MAC306892 MB C Glossary 32 RER620 Communication Protocol Manual ...

Page 39: ......

Page 40: ...istribution Automation 4300 Coral Ridge Drive Coral Springs FL 33065 USA Phone 1 800 523 2620 Phone 1 954 752 6700 Fax 1 954 345 5329 www abb com substationautomation 1MAC306892 MB C Copyright 2017 ABB All rights reserved ...

Reviews: