Section 6
Connecting
6.1
Making the electrical connection
6.1.1
IED connectors
SEMOD127536-1 v1
6.1.1.1
Overview
SEMOD129364-5 v1
The quantity and designation of connectors depend upon the type and size of the IED. The rear
cover plates are prepared with space for the maximum of HW options for each case size and
the cut-outs that are not in use are covered with a plate from factory.
Overview
M11562-3 v11
Table 2:
Basic modules
Module
Description
Power supply module (PSM)
Including a regulated DC/DC converter that supplies auxiliary
voltage to all static circuits.
•
An internal fail alarm output is available.
Numerical module (NUM)
Module for overall application control. All information is
processed or passed through this module, such as
configuration, settings and communication. The module
provides four SFPs for Ethernet traffic.
Analog digital conversion module (ADM)
The module converts the VT and CT analog signals from the
TRM to digital signals processed by the NUM. Carrier for
communication boards.
Note: TRM module is not included in SAM600-IO, so ADM
module is only used for internal communication carrier for IO
modules.
Table 3:
Application specific modules
Module
Description
Binary input module (BIM)
Module with 16 optically isolated binary inputs
Binary output module (BOM)
Module with 24 single outputs or 12 double-pole command
outputs including supervision function
Binary I/O module (IOM)
Module with 8 optically isolated binary inputs, 10 outputs and
2 fast signalling outputs.
Optical Ethernet module (OEM)
Module used for Ethernet traffic. It has support for two SFPs.
Optical Ethernet SFP
Small form factor pluggable for Ethernet communication
Galvanic RJ45 Ethernet SFP
Small form factor pluggable for Ethernet communication
mA input module (MIM)
Analog input module with 6 independent, galvanically
separated channels
Static output module (SOM)
Module with 6 fast static outputs and 6 change over output
relays
1MRK 514 030-UEN B
Section 6
Connecting
Switchgear control unit SAM600-IO
21
Installation manual
© Copyright 2017 ABB. All rights reserved