Table 156. Stabilized and instantaneous differential protection for two-winding transformers (TR2PTDF) main settings
Parameter
Function
Value (Range)
Step
High operate value
TR2PTDF
500...3000 %I
r
10
Low operate value
TR2PTDF
5...50 %I
r
1
Slope section 2
TR2PTDF
10...50%
1
End section 2
TR2PTDF
100...500 %I
r
1
Restraint mode
TR2PTDF
5 = Waveform
6 = 2.h + waveform
8 = 5.h + waveform
9 = 2.h + 5.h + wav
-
Start value 2.H
TR2PTDF
7...20%
1
Start value 5.H
TR2PTDF
10...50%
1
Operation
TR2PTDF
1 = on
5 = off
-
Winding 1 type
TR2PTDF
1 = Y
2 = YN
3 = D
4 = Z
5 = ZN
-
Winding 2 type
TR2PTDF
1 = y
2 = yn
3 = d
4 = z
5 = zn
-
Zro A elimination
TR2PTDF
1 = Not eliminated
2 = Winding 1
3 = Winding 2
4 = Winding 1 and 2
-
Table 157. Numerical stabilized low-impedance restricted earth-fault protection (LREFPNDF)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2 Hz
±2.5% of the set value or ±0.002 x I
n
Start time
1)2)
Minimum
Typical
Maximum
I
Fault
= 2.0 × set
Operate value
37 ms
41 ms
45 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5, …
1)
Current before fault = 0.0, f
n
= 50 Hz, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
1MRS759144 A
REX640
Product version: 1
78