Table 15. Single-pole power output relays
Description
Value
Rated voltage
250 V AC/DC
Maximum continuous burden (resistive load, AC)
2000 VA
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at
48/110/220 V DC
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
Table 16. Static signal output (SSO) relays
Description
Value
Rated voltage
250 V AC/DC
Maximum continuous burden (resistive load, AC)
250 VA
Continuous contact carry
1 A
Make and carry for 3.0 s
5 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at
110 V DC
>0.25 A
Minimum load current
1 mA
Maximum operation frequency at 50% duty cycle
10 Hz
Table 17. Double-pole power output relays with TCS function
Description
Value
Rated voltage
250 V AC/DC
Maximum continuous burden (resistive load, AC)
2000 VA
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at
48/110/220 V DC (two contacts connected in series)
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
Trip-circuit supervision (TCS):
• Control voltage range
20...250 V AC/DC
• Current drain through the supervision circuit
~1.5 mA
• Minimum voltage over the TCS contact
20 V AC/DC (15...20 V)
1MRS759144 A