2
2
sr
R
al
alreq
tf
ct
Lsw
pr
r
I
S
E
E
I
R
R
I
I
æ
ö
³
= ×
×
×
+
+
ç
÷
è
ø
EQUATION2241 V2 EN-US
(Equation 526)
Where:
I
tf
Maximum primary fundamental frequency three-phase fault current that passes the
CTs and the power transformer (A).
R
Lsw
The resistance of the single secondary wire and additional load (Ω).
In impedance grounded systems the phase-to-ground fault currents often are relatively
small and the requirements might result in small CTs. However, in applications where
the zero sequence current from the phase side of the transformer is a summation of
currents from more than one CT (cable CTs or groups of individual CTs in Holmgren
connection) for example, in substations with breaker-and-a-half or double-busbar
double-breaker arrangement or if the transformer has a T-connection to different
busbars, there is a risk that the CTs can be exposed for higher fault currents than the
considered phase-to-ground fault currents above. Examples of such cases can be cross-
country faults or phase-to-phase faults with high fault currents and unsymmetrical
distribution of the phase currents between the CTs. The zero sequence fault current
level can differ much and is often difficult to calculate or estimate for different cases.
To cover these cases, with summation of zero sequence currents from more than one
CT, the phase side CTs must fulfill the Requirement
2
sr
R
al
alreq
f
ct
L
pr
r
I
S
E
E
I
R
R
I
I
æ
ö
³
=
×
×
+
+
ç
÷
è
ø
EQUATION2242 V2 EN-US
(Equation 527)
Where:
I
f
Maximum primary fundamental frequency three-phase fault current that passes the
CTs (A)
R
L
The resistance of the secondary wire and additional load (Ω). The loop resistance
containing the phase and neutral wires shall be used.
25.1.7
Current transformer requirements for CTs according to other
standards
SEMOD53771-1 v1
M11623-4 v3
All kinds of conventional magnetic core CTs are possible to use with the IEDs if they
fulfill the requirements corresponding to the above specified expressed as the rated
equivalent limiting secondary e.m.f. E
al
according to the IEC 61869-2 standard. From
different standards and available data for relaying applications it is possible to
1MRK 504 163-UUS A
Section 25
Requirements
Transformer protection RET670 2.2 ANSI
993
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...