15.1.3.3
Single circuit breaker with double busbar, internal voltage selection
M12326-3 v7
lineVoltage/1/2/3
bus1
Voltage
bus2
Voltage
Bus
1
Bus
2
189
289
Line
V
REF
1
V
REF
2
VA/VB/VC
Fuse
VT
Fuse
VT
Fuse
VT
152
ANSI10000095-1-en.vsd
SESRSYN (25)
V3PB1*
V3PB2*
V3PL1*
V3PL2*
BLOCK
BLKSYNCH
BLKSC
BLKENERG
BUS1_OP
BUS1_CL
BUS2_OP
BUS2_CL
LINE1_OP
LINE1_CL
LINE2_OP
LINE2_CL
VB1OK
VB1FF
VB2OK
VB2FF
VL1OK
VL1FF
VL2OK
VL2FF
STARTSYN
TSTSYNCH
TSTSC
TSTENERG
AENMODE
MENMODE
SYNOK
AUTOSYOK
AUTOENOK
MANSYOK
MANENOK
TSTSYNOK
TSTAUTSY
TSTMANSY
TSTENOK
VSELFAIL
B1SEL
B2SEL
L1SEL
L2SEL
SYNPROGR
SYNFAIL
VOKSYN
VDIFFSYN
FRDIFSYN
FRDIFFOK
FRDERIVA
VOKSC
VDIFFSC
FRDIFFA
PHDIFFA
FRDIFFM
PHDIFFM
INADVCLS
VDIFFME
FRDIFFME
PHDIFFME
Vbus
VLine
MODEAEN
MODEMEN
ANSI10000095 V1 EN-US
Figure 310:
Connection of the SESRSYN function block in a single breaker, double
busbar arrangement with internal voltage selection
When internal voltage selection is needed, the voltage transformer circuit connections
are made according to figure
. The voltage from the busbar 1 VT is connected to
V3PB1 and the voltage from busbar 2 is connected to V3PB2. The voltage from the
line VT is connected to V3PL1. The positions of the disconnectors and VT fuses shall
be connected as shown in figure
. The voltage selection parameter
CBConfig
is set
to
Double bus
.
1MRK 504 163-UUS A
Section 15
Control
Transformer protection RET670 2.2 ANSI
687
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...