8.16.2
Application
SEMOD143248-4 v3
Normally, the generator operates synchronously with the power system, that is, all the
generators in the system have the same angular velocity and approximately the same
phase angle difference. If the phase angle between the generators gets too large the
stable operation of the system cannot be maintained. In such a case the generator loses
the synchronism (pole slip) to the external power system.
The situation with pole slip of a generator can be caused by different reasons.
A short circuit occurs in the external power grid, close to the generator. If the fault
clearance time is too long, the generator will accelerate so much, so the synchronism
cannot be maintained. The relative generator phase angle at a fault and pole slip,
relative to the external power system, is shown in figure
.
en06000313.vsd
IEC06000313 V1 EN-US
Figure 234:
Relative generator phase angle at a fault and pole slip relative to the
external power system
The relative angle of the generator is shown for different fault duration at a three-phase
short circuit close to the generator. As the fault duration increases the angle swing
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
467
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...