Object type Addr
IEC 61850 name
SA name
Description
Values
1
47
.Op.phsB
- phsB Operate
1=Operate
1
48
.Op.phsC
- phsC Operate
1=Operate
1
49
.Op.neut
- neut Operate
1=Operate
2.4
Measurands
2.4.1
Supported ASDU types
The Object type column contains an internal type identification for the data objects.
Internal object types in turn can be configured into different IEC 60870-5-101/104
ASDU data types.
For measurand values, the object type code also reflects which value coding
variation the object has as default.
Table 81:
Supported ASDU types in monitoring direction
Object
type
Description
IEC 60870-5-101/104 ASDU alternatives
Interrogated
Change event
ASDU
Type string
ASDU
Type string
20
Measurand,
floating point
13
M_ME_NC_1
14
M_ME_TC_1
1)2)
36
M_ME_TF_1
2)3)
21
Measurand,
normalized
9
M_ME_NA_1
10
M_ME_TA_1
1)2)
34
M_ME_TD_1
2)3)
22
Measurand,
scaled value
11
M_ME_NB_1
12
M_ME_TB_1
1)2)
35
M_ME_TE_1
2)3)
1) Requires setting parameter
Time Format to be in mode “Short 24 bits”
2) The stack supports point-dependent value format changing between all three measurand formats. In
PCM600 each measurand object occurs in three interchangable format instances.
3) Requires setting parameter
Time Format to be in mode “Full 56 bits”
2.4.2
General device data
Table 82:
General device data
Object type Addr
IEC 61850 name
SA name
Description
Values
CTRL.LLN0
20
10002
LocRem.stVal
Local/Remote state analog
0=Off; 1=Local;
2=Remote; 3=Station
LD0.LLN0
21
40000
.ActSG.stVal
Active setting group
1...6
DR.RDRE1
Table continues on next page
1MRS757824 C
Section 2
IEC 60850-5-101/104 data mappings
Recloser Protection and Control RER615
39
Point List Manual