Parameter
Values (Range)
Unit
Step
Default
Description
UR offline interval
0...65535
min
1
15
Unsolicited offline interval
UR Class 1 Min events
0...999
1
2
Min number of class 1 events to
generate UR
UR Class 1 TO
0...65535
ms
1
50
Max holding time for class 1 events to
generate UR
UR Class 2 Min events
0...999
1
2
Min number of class 2 events to
generate UR
UR Class 2 TO
0...65535
ms
1
50
Max holding time for class 2 events to
generate UR
UR Class 3 Min events
0...999
1
2
Min number of class 3 events to
generate UR
UR Class 3 TO
0...65535
ms
1
50
Max holding time for class 3 events to
generate UR
Legacy master UR
1=Disable
2=Enable
1=Disable
Legacy DNP master unsolicited mode
support. When enabled relay does not
send initial unsolicited message.
Legacy master SBO
1=Disable
2=Enable
1=Disable
Legacy DNP Master SBO sequence
number relax enable
Default Var Obj 01
1...2
1
1
1=BI; 2=BI with status.
Default Var Obj 02
1...2
1
2
1=BI event; 2=BI event with time.
Default Var Obj 30
1...4
1
2
1=32 bit AI; 2=16 bit AI; 3=32 bit AI
without flag; 4=16 bit AI without flag.
Default Var Obj 32
1...4
1
4
1=32 bit AI event; 2=16 bit AI event;
3=32 bit AI event with time; 4=16 bit AI
event with time.
1MRS757820 B
Section 4
DNP3 parameters
Recloser Protection and Control RER615
23
Communication Protocol Manual