Table 6:
Analog inputs
Description
Values
Static (steady-state) object number
30
Static variation reported when variation 0
requested (default setting)
2 (16-bit analog input)
Change event object number
32
Change event variation reported when variation
0 requested (default setting)
4 (16-bit analog input change with time)
Table 7:
Default Class assignment for analog input data
Point index
Name/description
Default deadband
Default change event
assigned class (1, 2, 3 or
none)
See the point list manual.
Configurable IED setting
2
3.2.3.1
Analog data scaling
The four scaling options associated with analog input data reporting are None,
Ratio, Multiplicative and Divisor. The selection
None
means that no scaling is
performed on the source IEC 61850 value. The value is reported as such to DNP3.
Ratio, multiplicative and divisor scaling methods
The PCM600 tool contains four value arguments related to the scaling methods:
sourceMinVal
,
sourceMaxVal
,
destMinVal
and
destMaxVal
. The use of these
arguments differs depending on the scaling method.
The ratio, multiplicative and divisor scaling methods use the first two arguments,
souceMinVal
and
sourceMaxVal
, to define the source value range inside which the
object is to be used. The complete value range of the object is usually wanted even
though the user could freely define the source range.
Arguments three and four,
destMinVal
and
destMaxVal
, define the destination
value range. In ratio scaling, arguments
destMinVal
and
destMaxVal
define the
corresponding range of the scaled, reported DNP3 value.
DNPvalue=
(sourceValue - sourceMinVal)
(destMaxVal-destMinV
Val)
+destMinVal
(sourceMaxVal - sourceMinVal)
GUID-9F985816-2268-412A-AE24-ED90EAC44AD7 V2 EN
(Equation 1)
In multiplicative scaling, argument four
destMaxVal
becomes a scale constant and
argument three
destMinVal
becomes an offset.
DNPvalue
sourceValue
destMaxVal
destMinVal
=
×
+
(
)
GUID-4CB1987F-BDD8-48A2-9389-20B0B2EB271F V1 EN
(Equation 2)
1MRS757820 B
Section 3
Vendor-specific implementation
Recloser Protection and Control RER615
15
Communication Protocol Manual