Operate area
Instrument
transformer
angle error
3I
0
(prim)
3I
0
(to prot)
Characteristic after
angle compensation
RCAcomp
IEC06000651-3-en.vsd
RCADir
= 0º
IEC06000651 V3 EN
Figure 179:
Explanation of RCAComp
Directional residual power protection measuring 3I
0
· 3U
0
· cos φ
φ is defined as the angle between the residual current 3I
0
and the reference voltage
(U
ref
= -3U
0
e
-jRCA
) compensated with the set characteristic angle
RCADir
(|
φ=ang(3I
0
)—ang(U
ref
)|). The function operates when 3I
0
· 3U
0
· cos φ gets larger than
the set value
SN>
. Refer to the simplified logical diagram in Figure
For trip, the residual power 3I
0
· 3U
0
· cos φ, the residual current 3I
0
and the release
voltage 3U
0
, shall be larger than the set levels (
SN>
,
INRel>
and
UNRel>
).
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function picks up, binary output signals START and STDIRIN are
activated. If the output signals START and STDIRIN remain active for the set delay
tDef
or after the inverse time delay (setting
kSN
) the binary output signals TRIP and
TRDIRIN get activated.
The function shall indicate forward/reverse direction to the fault. Reverse direction is
defined as 3I
0
· 3U
0
·cos (φ + 180°)
³
the set value.
Section 8
1MRK502052-UEN B
Current protection
396
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...